A Three-Port Photovoltaic (PV) Micro-Inverter with Power Decoupling ...

4 downloads 0 Views 879KB Size Report
Inverter with Power Decoupling Capability. Souhib Harb, Haibing Hu, Nasser Kutkut, Issa Batarseh, Z. John Shen. Department of Electrical Engineering and ...
A Three-Port Photovoltaic (PV) MicroInverter with Power Decoupling Capability Souhib Harb, Haibing Hu, Nasser Kutkut, Issa Batarseh, Z. John Shen Department of Electrical Engineering and Computer Science University of Central Florida Orlando, FL 32826 ABSTRACT: This paper presents a new micro-inverter topology that is intended for single-phase grid-connected PV systems. The features of the proposed topology are: (1) eliminating the double-frequency power ripple using small film capacitor; (2) improving the maximumpower-point tracking (MPPT) performance; (3) using long life-time film capacitors, which will improve the reliability of the inverter; and (4) requiring no additional circuitry to manage the transformer leakage energy. Index terms- Power Decoupling, Single phase Inverter, Photovoltaic, Microinverter Fig 1: Input and output power waveforms.

I. INTRODUCTION Micro-Inverters connected to a single PV panel are becoming the trend for the future of grid-connected PV systems for a number of reasons including: (1) improved energy harvest; (2) improved system efficiency; (3) lower installation costs; (4) plug-N-play operation; (5) and enhanced flexibility and modularity. Typically, the microinverter is connected, and even attached, to a single PV panel, which requires that the micro-inverter to have a lifespan matching the PV panel’s life-span, namely 25 years. [1]. In single-phase grid-connected micro-inverters, the MPPT provides constant output power from the PV panel while the injected power to the grid is following a squared sine wave. _

Usually, a capacitor is connected in parallel with the PV panel, which results in a very large capacitance since the allowable voltage ripple must be held to very low values ( Pin , the circuit will be operating in mode-II (discharging mode). The decoupling capacitor will support the PV panel by discharging energy into the transformer and transferring the required power to the output (utility grid).

2

(4)

Note: V0 sin(ω0 t ) can be considered as a constant value given a very small switching cycle (Ts) compared to the output AC cycle (T0). At this point, one of the AC side switches will be turned on (depending on the polarity of the output voltage), Figure 3c. The power will be transferred to the AC output side.

Mode-I This mode is divided into three circuit modes, as shown in Fig.3: (1) storing energy into the transformer’s magnetizing inductance; (2) charging the decoupling capacitor; (3) and transferring the power to the output.

204

Using the power equation, ILP can be derived as 1 2

1 2

Mode-II This mode is also divided into three circuit modes, as shown in Fig. 5. The first and the third modes are similar to the previous modes. In the second mode, the decoupling capacitor will be discharging its energy into the transformer’s magnetizing inductance. The transformer’s magnetizing current will be charged from the PV panel by turning S1 on, Fig. 5a. When the magnetizing current reaches the first peak value, given in (9), S2 is turned on and the second mode starts at this point of time, Fig. 5b.

(5)

It can be found that (6)

(7) 2

(9)

Substituting (6) and (7) in (5), then: 2

1

The transformers’ magnetizing current will continue charging from the decoupling capacitor until it reaches the second peak value which is given in (4). At this time both S1 and S2 are turned off (Fig. 5c) and the power is transferred to the output side through one of the AC side switches. Fig. 4 shows the magnetizing current, the input and secondary side currents waveforms, and the switches driving signals.

(8)

Fig. 4 shows the operating waveforms during this mode including the magnetizing current, the input and secondary side current waveforms, and the switches’ driving signal.

(a)

(b)

(c) Fig 5: Operation modes during discharging mode (mode-II).

Fig 4: Inductor current, Input current, output current waveforms, S1, S2, S3 gate signals for the two main operation modes.

205

frequency of 110Vrms and 60Hz, respectively. Let us choose a DC-level across the decoupling capacitor of 120V. Then the ripple should be less than 107V. Assuming a value of 100V and using (2), 22.1µF of decoupling capacitance is needed.

It can be noticed from the operation modes that the leakage energy is stored in the decoupling capacitor without using any additional circuit. This is one of the advantages of the proposed topology. In [5], this leakage energy will cause a spike on the decoupling switch at turn off time when the energy is transferred to the AC side. The modified topology in [6] solved this problem by storing the leakage energy in the decoupling capacitor through the flyback diodes. The advantages of the proposed topology over the previous topologies in [5] [6] can be summarized as follows: 1. 2.

3.

V. SIMULATION RESULTS The PSIM software is used to simulate the proposed topology. Table 1 lists the components’ values that were used in the simulation. Table 1: Proposed topology component values.

No double power conversion, which results in reduced power losses. The transformer leakage energy is stored in the decoupling capacitor through D1. This means that there is no need for extra dissipative clamp circuits. Again, this will reduce the power losses. Fewer components are used in the decoupling circuit, only one switch and two diodes, unlike the topology in [6], where four switches and two diodes are required.

Input Power (Pin) Magnetizing Inductance (Lm) Decoupling Capacitance (CD) Output Resistor (Ro)

Input Voltage (Vin)

35 V

7µH

Turns Ration (N)

5

40µF

Cf

1µF

120Ω

Lf

1mH

Fig. 6 shows the simulation results. In Fig. 6, the magnetizing inductance, input, and secondary currents waveforms for one complete grid cycle are shown.

IV. THE DECOUPLING CAPACITOR (CD) The formula that governs the decoupling capacitor (CD) value will be derived in this section. During submode-3 in both main modes, the energy that has been stored in the magnetizing inductance will be transferred to the secondary side. Wherefore, the voltage across the decoupling capacitor must be greater than the stress voltage across S1, which is given in (10). 2

100 W

Magnetizing inductance current, iLm(t)

Input current, iin(t)

(10)

Secondary side current, i2(t)

Then, the minimum voltage across CD must satisfy the following condition (11). Fig 6: Simulation results of the proposed topology.

(11)

Fig. 7 and Fig. 8 show an expanded view of the circuit operation in mode-I and mode-II, respectively.

But, the minimum voltage across CD is given in (12). ∆

(12) 2 Using (11) and (12), the relationship in (13) can be derived. By choosing a certain DC-level across the CD, the maximum allowed voltage ripple can be found. ∆

2

(13)

It is worth to mention that when we choose the DClevel voltage across the decoupling capacitor we should take in the consideration the stresses on the power devices at the input side (S1, S2, D1, and D2). Now, for a certain system parameters, we can choose the appropriate value for the decoupling capacitor. Consider a 100W system with 35V as an input voltage with a grid voltage and

Fig 7: Expanded view for the simulation results for mode-I.

206

Fig.10: Power stage circuit for verification purposes.

Fig.11 shows the driver signals in Mode I operation, during which the switch S2 is always off. When switch S1 turns off, the energy stored in the magnetizing inductance is transferred to the capacitor CD and switch S3 turns on when the current falls to certain level. The current waveforms, both in transformer primary side and secondary side, are depicted in Fig.12. Fig.13 shows the driver signals in Mode II operation, during which the switch S3 is always on. The energy stored in the capacitor increases the magnetizing current by turning on the switch S2 as shown in Fig.14. All these driver signals are calculated and generated by STM32 ARM based on the reference current, input DC voltage and capacitor voltage.

Fig 8: Expanded view for the simulation results for mode-II.

, Fig. 9 shows the output current, output voltage, , and finally the input the stress voltage across S1 and and output power waveforms.

S1 S2

S3

Fig 9: Output current and voltage, VCD, the stress voltage across S1 and VCD, and finally the input and output power waveforms.

VI. EXPERIMENTAL RESULTS A prototype was set up to verify the validity of the proposed topology. To simplify the verification, the power circuit for the topology, shown in Fig.10, with an open loop control strategy is employed. The key parameters are listed in table 2.

Fig.11: Driver signals in Mode 1

Table 2: The experimental parameters' values. Input voltage

20V

Switching frequency

100KHz

Magnetizing inductance

7.6uH

Transformer turn ratio

1:1

R0

40Ω

CD

50uF

Cr

1uF

Current at primary side Current at secondary side

Fig.12: the current waveforms in both primary and secondary sides

207

S1

instead of electrolytic capacitor. Hence, it will have a long life-span comparable to the PV panel. The transformer leakage energy is handled by the decoupling circuit itself so there is no need for additional dissipative circuits; which leads to reduced power losses and improved efficiency.

S3

S2

REFERENCES [1] S.B.Kjaer, J.H.Pedersen, F. Blaabjerg. “A Review of SinglePhase Grid-connected Inverters for Photovoltaic Modules”. IEEE Trans. Industry Applica. Vol.41 no.5, pp.1292-1306, Sept. 2005. [2] S. B. Kjaer, “Design and control of an inverter for photovoltaic applications,” Ph.D. dissertation, Inst. Energy Technol., Aalborg University, Aalborg East, Denmark, 2004/2005. [3] www.CDE.com// Type 381EL 1050C Ultra-Long Lift Snap-In, Aluminum. [4] A.C. Kyritsis, N. P. Papanikolaou, E. C. Tatakis. “A novel Parallel Active Filter for Current Pulsation Smoothing on Single Stage Grid connected AC-PV Modules”, in Proc. European Conf. Power Electronics and Applications (EPE), 2007. [5] T. Shimizu, K. Wada, and N. Nakamura, “Flyback-type singlephase utility interactive inverter with power pulsation decoupling on the dc input for an ac photovoltaic module system,” IEEE Trans. Power Electron., vol. 21, no. 5, pp. 1264–1272, Sep. 2006. [6] S. B. Kjaer and F. Blaabjerg, "Design optimization of a single phase inverter for photovoltaic applications," in Proc. IEEE Power Electronics Specialists Conference, 2003, vol. 3, pp. 1183-1190. [7] G. H. Tan, J. Z. Wang, and Y. C. Ji, “Soft-switching flyback inverter with enhanced power decoupling for photovoltaic applications,” IET Trans. Elect. Power Appl., vol. 1, no. 2, pp. 264–274, Mar. 2007. [8] P. Enjeti and W. Shireen, “A new technique to reject DC link voltage ripple for inverters operating on programmed PWM waveforms,” IEEE Trans. on Power Electronics, VOL. 7, NO. 1, Jan. 1992.pp.171-180. [9] T. Brekken. N. Mohan, C. Henze, & L.R. Moumneh, "Utilityconnected power converter for maximizing power transfer from a photovoltaic source while drawing ripple-free current," IEEE PESC, 2002.pp.1518-1522. [10] N. A. Ninad, L. Lopes, “A Low Power single-Phase Utility Interactive Inverter for Residential PV Generation with Small DC Link Capacitor” [11] P. T. Krein and R. S. Balog, "Cost-effective hundred-year life for single-phase inverters and rectifiers in solar and LED lighting applications based on minimum capacitance requirements and a ripple power port," IEEE Applied Power Electronics Conference, 2009. [12] Al-Atrash, H.; Tian, F.; Batarseh, I., “Tri-Modal Half-Bridge Converter Topology for Three-Port Interface,” IEEE Trans. Power Electronics, vol. 22, pp. 341 - 345, January 2007. [13] Q. Li, P. Wolfs, and S. Senini, “A hard switched high frequency link converter with constant power output for photovoltaic applications,” in Proc. Australasian Univ. Power Eng. Conf., 2002. [14] C. Bush, B. Wang. “A Single-Phase Current Source Solar Inverter with Reduced-Size DC Link” IEEE Energy conversion congress and Exposition, San Jose,CA, 2009,pp.54-59. [15] H. Hu, S. Harb, N. Kutkut, I. Batarseh, Z. J. Shen, “Power Decoupling Techniques for Micro-inverters in PV Systems-a Review”, IEEE Energy conversion congress and Exposition, 2010.

Fig 13: Driver signals in Mode 2

id

id

Current at primary

Current at secondary

Fig.14: Current waveforms in Mode II

Voltage across Cd

Output voltage

Fig. 15: output voltage and voltage across the decoupling capacitor

The output voltage as shown in Fig.15 is rectified sinsoidal waveform. Some slight distortions can be noticed during mode transitions due to nonideal factors such existance of leakage inductance, switch transients and calculation errors in the MCU. The voltage across the decoupling capacitor fluctates according to charging and discharging process. As shown in Fig. 15, at the point where the operation mode switches from mode I to mode II, the voltage across the capacitor is charged to maximum and the minimal voltage occurs at mode transition point from mode II to mode I.

[16] Zhijun Qian; Abdel-Rahman, O.; Al-Atrash, H.; Batarseh, I.; , "Modeling and Control of Three-Port DC/DC Converter Interface for Satellite Applications," Power Electronics, IEEE Transactions on , vol.25, no.3, pp.637-649, March 2010

VII. CONCLUSION

[17] Zhijun Qian; Abdel-Rahman, O.; Hu, H.; Batarseh, I.; , " An Integrated Three-port Inverter for Stand-alone PV Applications," Energy Conversion Congress and Exposition, 2010. ECCE 2010. IEEE , vol., no., pp.1471-1478, 12-16 Sept. 2010

A new micro-inverter topology is presented. It is primarily intended for the AC-Module PV systems. The proposed topology employs new power decoupling technique where a small film capacitor can be used

208