Cables according to Overseas standards

29 downloads 2107 Views 2MB Size Report
CEI. Comitato Elettrotecnico Italiano. CSA. Canadian Standard Association .... CEI, PVC-single cores according to Italian Standard . ... FROR CEI 20 – 22 II .
Cables according to Overseas standards

F

â

Cables according to Overseas standards The installation of cables and wires according to overseas standards are getting more and important for the machine and plant industries. HELUKABELâ knows this problem from his customers and delivers since long time single core and multicore cables according to the following standards. Due to our extensive stock capacity, we are in a position to cover your requirements quick and correctly.

F

Please enquire to our sales department. UL AWM MTW CEI CSA SEV USASI CNOMO

Underwriters Laboratories Inc. Appliance Wiring Material Machine Tool Wire Comitato Elettrotecnico Italiano Canadian Standard Association Schweizerischer Elektrotechnischer Verein USA Standard Institute Comite´ De Normalisation Des Moyens De Production

â

F

Contents and Index Description/standards F

Type

Page

Cables according to overseas standards

UL-CSA, PVC-single cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL-CSA, PVC-single cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HAR-UL-CSA, PVC-single cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HAR-UL-CSA-AWM-MTW, PVC-single cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL, PVC + Nylon-single cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL-CSA, Polyolefin-single cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL-CSA, Polyolefin-single cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL, PVC control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL, PVC control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL, PVC control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL, PVC control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL, PVC control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL, PVC control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL-CSA, Rubber control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CEI, PVC-single cores according to Italian Standard . . . . . . . . . . . . . . . . . . . . CEI, Control cable according to Italian Standard . . . . . . . . . . . . . . . . . . . . . . . . . C.N.O.M.O. Control cable according to French Standard. . . . . . . . . . . . . . . PVC-Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PVC-Power Cable screened. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UL-AWM 1007, CSA-AWM, 300 V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 1 UL-AWM/MTW 1015, CSA-AWM, 600 V . . . . . . . . . . . . . . . . . . . . . F 2 THREENORM HAR-UL-CSA, 300 V to 750 V . . . . . . . . . . . . . . . F 3 FIVENORM HAR-UL-CSA-AWM-MTW . . . . . . . . . . . . . . . . . . . . . . . . . . F 4 THHN/THWN, 600 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 5 HELUTHERM 145, 300 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 6 HELUTHERM 145, 600 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 7 Style 2464 / 300 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 8 Style 2516 / 600 V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 9 Style 2464 / 300 V, Cu-screened. . . . . . . . . . . . . . . . . . . . . . . . . . . F 10 Style 2516 / 600 V, Cu-screened. . . . . . . . . . . . . . . . . . . . . . . . . . . F 11 Style 2464 / 300 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 12 Style 2464 / 300 V, Cu-screened. . . . . . . . . . . . . . . . . . . . . . . . . . . F 13 SJO / 300 V, SO / 600 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 14 CEI 20 – 22 II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 15 FROR CEI 20 – 22 II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 16 N05V V5-F accord. to standard NFC 32 – 206 . . . . . . . . . F 17 JZ-604 TC TRAY CABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 18 – F 19 JZ-604-YCY TRAY CABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F 20 – F 21

Works photo: HELUKABELâ

â

HELUKABEL is not only selling cables and wires for all fields of communication techniques, but they are also using exhibitions as a medium of communication all over the world. The active and regular participation on exhibitions is an essential part of our Marketing-Mix.

F

Exhibitions are seen as an information and Communication Centre which allow HELUKABELâ to be at the forefront of the competitive market. Because national and international exhibition participations are an answer for your cable enquiries. â

UL-Style 1007, CSA TR 64

300 V

PVC-single cores, UL-CSA approved, 808 C

Technical data

Cable structure*

Application

PVC-insulated jumper wire to UL-Style and CSA-AWM * UL-Style 1007 * CSA-AWM I A/B or TR 64 – Temperature range flexible – 58 C bis +808 C fixed installation –308 C bis +808 C CSA-AWM I A/B or TR 64 +908 C – Nominal voltage 300 V – Test voltage 2000 V – Test voltage (Spark test) AWG 26 – 20 = 4 kV AWG 10 – 18 = 5 kV – Bending radius once ca. 5 x cable 1 multiple ca. 10 x cable 1

– Stranded copper conductor, tinned to UL-Std. 785 section G – PVC-core insulation according to UL-Std. 1587 class 43 Tab. 50.182, heat and damp resistant – PVC self-extinguishing and flame retardant, test method to UL V W-1/CSA FT1

For the internal wiring of switchbords, electrical equipment, e. g. households, radio or televisions and control desks. Connecting wires in machines laid in protective tubes and flexible pipes and also for motors and transformators.

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers Standards = Underwriters Laboratories Inc. UL (USA) CSA = Canadian Standards Association (Canada)

AWM: Appliance Wiring Material For internal wirings for electrical equipment and control apparatus e. g. electronic assembly components. Resistance Conditionally resistant to – Oils – Solvents – Acids – Lyes

F

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

AWGno.*)

crosssection ca. mm2

Outer 1 ca. mm

Cop kg / km

Weight ca. kg / km

635 620 621 622 623 624 636 637 638

26 24 22 20 18 16 14 12 10

0,13 0,21 0,33 0,52 0,82 1,32 2,08 3,31 5,26

1,3 1,4 1,6 1,9 2,2 2,5 3,0 3,9 4,1

1,6 2,3 3,4 5,3 8,2 13,0 20,0 33,0 51,6

3,2 4,3 6,0 8,5 12,5 18,5 29,0 40,0 61,0

Preis DM / 100 m Cu 300, –

Style 1569, +808 C/+908 C/+1058 C on request.

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15. " You can find further information regarding UL/CSA-Cables on pages T 71 – T 77. Please complete the above part-no. for the colour required, using the following table: 00 green 01 black 02 blue 03 brown 04 red 05 white 06 grey 07 violet 08 yellow 09 orange 10 transparent 11 pink 12 beige 13 green-yellow

* Due to design the constructional alternations may the possible. ** Plain copper conductor on request PVC cables will be changed to lead free PVC successively. For further single cores see the following pages: – for PVC, see pages D 1 – D 10. – for PUR, see page G 32. – for rubber, see pages G 31, O 15. – halogen-free, see pages G 23 – G 24, E 5, E 15 – E 16, E 24 – E 26. – heat-resistant, see pages E 5 – E 6, E 10 – E 11, E 13 – E 16, E 21, E 23 – E 25. – vehicle cables, see pages K 1 – K 4. Further sizes and jacket colours available on request. Type THHN, TEW-AWM see page F 5. Further types on request..

â

F1

UL-Style 1015

600 V PVC-Single Cores, UL/CSA approved

Technical data

Cable structure*

Application

– PVC-insulated jumper wire as per UL AWM Style 1015/MTW and CSA-AWM/TEW * as per UL-Style 1015 and CSA-TEW – Temperature range flexible – 58 C to +1058 C fixed installation –308 C to +1058 C – Temperature at conductor max. UL and CSA: +1058 C – Nominal voltage 600 V – Test voltage (Spark test) AWG 24 : 4 kV AWG 22 and 20 : 5 kV AWG 18 to 10 : 6 kV ^ AWG 8 : 7,5 kV

– Stranded copper conductor, tinned or plain**, AWG-sizes as per table below – PVC-core insulation according to UL-Standard 1581, class 43 and CSAC22.2 No. 210 UL V W-1 and CSA FT1, heat and damp resistant – PVC self-extinguishing and flame retardant, test method to UL V W-1

For the internal wiring of switchbords, electrical equipment, e. g. households, radio or televisions and control desks. Connecting wires in machines laid in predective tubes and flexible pipes and also for motors and transformators.

* *

UL-type AWM + MTW CSA-type AWM + TEW

1058 C 600 V 1058 C 600 V

– Bending radius once ca. 5 x cable 1 multiple ca. 10 x cable 1

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers Standards = Underwriters Laboratories Inc. UL (USA) CSA = Canadian Standards Association (Canada)

UL bzw. CSA: AWM: Appliance Wiring Material For internal wirings for electrical equipment and control apparatus e. g. electronic assembly components. UL-MTW: Machine Tool-Wires CSA-TEW: Equipment/Lead Wires MTW: Machine Tool Wire For the electronical installation of machine tools and the relative control Resistance Conditionally resistant to – Oils – Solvents – Acids – Lyes

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

UL/CSA AWM = 1058C, UL MTW, CSA TEW = 1058 C, 600 V Part No.

AWGno.*)

as per UL-AWM MTW

CSA AWM TEW

crosssection ca. mm2

601 602 603 604 605 606 607 608

24 22 20 18 16 14 12 10

1015/MTW 1015/MTW 1015/MTW 1015/MTW 1015/MTW 1015/MTW 1015/MTW 1015/MTW

AWM/TEW AWM/TEW AWM/TEW AWM/TEW AWM/TEW AWM/TEW AWM/TEW AWM/TEW

0,21 0,33 0,52 0,81 1,31 2,08 3,32 5,26

2,2 2,4 2,5 2,8 3,0 3,6 4,2 4,8

2,3 3,2 5,0 7,9 12,6 20,7 33,0 51,6

8 10 12 16 22 31 45 65

609

8

1015/MTW

AWM/TEW

8,35

6,4

80,6

110

610 611 612 613

6 4 3 2

1015/MTW 1015/MTW 1015/MTW 1015/MTW

AWM/TEW AWM/TEW AWM/TEW AWM/TEW

13,29 21,14 26,65 33,61

8,2 9,3 9,5 11,8

125,0 201,0 253,0 317,0

175 260 340 380

614 615 616 617 618

1 1/0 2/0 3/0 4/0

1015/MTW 1015/MTW 1015/MTW 1015/MTW 1015/MTW

AWM/TEW AWM/TEW AWM/TEW AWM/TEW AWM/TEW

42,38 53,47 67,40 84,97 107,17

14,0 15,0 16,0 18,5 20,2

399,0 500,0 631,0 792,0 996,0

500 615 750 900 1070

62501 62601 62701 62801 62901

250 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil

1015/MTW 1015/MTW 1015/MTW 1015/MTW 1015/MTW

127 152 178 203 254

" You can find further information regarding UL/CSA-Cables on pages T 71 – T 77. Type THHN, TEW-AWM see page F 5. Please complete the above part no. for the colour required, using the following table: 00 green 06 grey 12 beige 01 black 07 violet 13 green-yellow 02 blue 08 yellow 14 blue/white 03 brown 09 orange 15 dark blue 04 red 10 transparent 05 white 11 pink

F2

Outer 1 ca. mm

Cop kg / km

Weight ca. kg / km

Preis DM / 100 m Cu 300, –

19,6 1178,0 1280 20,9 1410,0 1518 22,2 1645,0 1756 24,5 1902,0 2002 25,8 2345,0 2475 * Due to design the constructional alternations may be possible. ** Plain copper conductor on request (cross-section in metric dimensions). PVC cables will be changed to lead free PVC successively. For further single cores see the following pages: – for PVC, see pages D 1 – D 10. – for PUR, see page G 32. – for rubber, see pages G 31, O 15. – halogen-free, see pages G 23 – G 24, E 5, E 15 – E 16, E 24 – E 26. – heat-resistant, see pages E 5 – E 6, E 10 – E 11, E 13 – E 16, E 21, E 23 – E 25. – vehicle cables, see pages K 1 – K 4. Further sizes and jacket colours available on request. *) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

â

â

HELUKABEL THREENORM

HAR-UL-CSA PVC-Single cores, UL-Style 1011 and CSA 600 V

Technical data

Cable structure

Application

– PVC-single cores according to DIN VDE 0281 part 3 and HD 21.3 S3 UL-Style 1011 and CSA, CSAAWM I/A/B 2 – Temperature range ) * H05 V-K/H07 V-K flexing + 58 C to +708 C fixed installation –108 C to +708 C * UL/CSA +808 C – Nominal voltage H05 V-K U0/U 300/500 V (# 1 mm2) H07 V-K U0/U 450/750 V ($ 1,5 mm2) UL/CSA 600 V AC – Test voltage H05 V-K/H07 V-K 2000 V – Spark Test AWG 20 : 5 kV .AWG 20 : 6 kV – Insulation resistance min. 20 MOhm x km – Minimum bending radius for permanent bending ca. 10 – 15 x core 1

1 – Bare copper fine wire ) stranded to DIN VDE 0295 cl. 5, BS 6360 cl. 5, HD 383 and IEC 60228 cl. 5 UL-Subject 758 Section G resp. ASTM B 174 – PVC core insulation TI1 to DIN VDE 0281 part 1 and UL-Std. 1581, class 43, CSA-C 22.2 No. 210 Tab. 12 class H – Core colours to DIN VDE 0293 – PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B),UL-V W1 CSA FT1

Three norms approved connecting jumper wire primarily designed for exportes, used in machine tools. This wire is used for internal wiring of switchboards and electrical equipment. The approbation of HAR-UL-CSA AWM make possible an economical storekeeping and simplification of parts list.

F

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers **) Note AWG equivalet values – see page T 15.

1

) Tinned conductor on request

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Type crosssec.

Outer 1

mm

Cop. weight kg/km

ca. RAL H05 V-K/mm2 Part No. 0,5/AWG 20 2,5 Part No. 0,75/AWG 19 2,65 Part No. 1/AWG 18 2,8 H07 V-K/mm2 Part No. 1,5/AWG 16 3,05 Part No. 2,5/AWG 14 3,6 Part No. 4/AWG 12 4,1 Part No. 6/AWG 10 4,8 Part No. 10/AWG 8 6,4 Part No. 16/AWG 6 8,1 Part No. 25/AWG 4 9,6 Part No. 35/AWG 2 10,8 Part No. 50/AWG 1 13,6 Part No. 70/AWG 2/0 15,2 Part No. 95/AWG 3/0 16,8 Part No. 120/AWG 4/0 19,5 Part No. 150/300 kcmil 22,2

blackwhite

gn-ye

blue

brown

red

white

grey

viol.

yellow

pink

green

trans.

dark blue

orange

other colours

twintone

9005

6018/ 1021

5015

8003

3000

1013

7000

4005

1021

3015

6018



5010

2003





63815

63816

63817

63818

63819

63820

63821

63822

63823

63824

63825

63826

63827

63828

63829

63830

63831

63832

63833

63834

63835

63836

63837

63838

63839

63840

63841

63842

63843

63844

63845

63846

63847

63848

63849

63850

63851

63852

63853

63854

63855

63856

63857

63858

63859

63860

63861

63862

63863

63864

63865

63866

63867

63868

63869

63870

63871

63872

63873

63874

63875

63876

63877

63878

63879

63880

63881

63882

63883

63884

63885

63886

63887

63888

63889

63890

63891

63892

63893

63894

63895

63896

63897

63898

63899

63900

63901

63902

63903

63904

63905

63906

63907

63908

63909

63910

63911

63912

63913

63914

63915

63916

63917

63918

63919

63920

63921

63922

63923

63924

63925

63926

63927

63928

63929

63930

63931

63932

63933

63934

63935

63936

63937

63938

63939

63940

63941

63942

63943

63944

63945

63946

63947

63948

63949

63950

63951

63952

63953

63954

63955

63956

63957

63958

63959

63960

63961

63962

63963

63964

63965

63966

63967

63968

63969

63970

63971

63972

63973

63974

63975

63976

63977

63978

63979

63980

63981

63982

63983

63984

63985

63986

63987

63988

63989

63990

4,8 7,2 9,6

14,4 24,0 38,0 58,0 96,0 154,0 240,0 336,0 63991

63992

63993

63994

63995

63996

63997

63998

63999

64000

64001

64002

64003

64004

64005

64006

64007

64008

64009

64010

64011

64012

64013

64014

64015

64016

64017

64018

64019

64020

64021

64022

64023

64024

64025

64026

64027

64028

64029

64030

64031

64032

64033

64034

64035

64036

64037

64038

64039

64040

64041

64042

64043

64044

64045

64046

64047

64048

64049

64050

64051

64052

64053

64054

64055

64056

64057

64058

64059

64060

64061

64062

64063

64064

64065

64066

64067

64068

64069

64070

480,0 672,0 912,0 1152,0 1440,0

PVC cables will be changed to lead free PVC successively. 2

) The cross-sections 0,5, 0,75 and 1,0 mm2 are according to H05 V-K, the cross-sections 1,5 up to 120 mm2 according to H07 V-K.

â

F3

â

HELUKABEL FIVENORM

HAR-UL-CSA-AWM-MTW PVC-Single cores, UL-Style 1015/UL-Standard 1063, 600 V 1058 C

Technical data

Cable structure

Application

– PVC-single cores according to DIN VDE 0281 part 3 and HD 21.3 S3, UL-Std. 1063, UL-Style 1015 and CSA-TEW and CSA-AWM I/A/B 2 – Temperature range ) * H05 V2-K/H07 V-K flexing + 58 C to + 908 C fixed installation –108 C to +1058 C * UL/CSA +1058 C – Nominal voltage H05 V2-K U0/U 300/500 V (# 1 mm2) H07 V2-K U0/U 450/750 V ($ 1,5 mm2) UL/CSA 600 V AC, 750 V DC – Test voltage H05 V2-K/H07 V2-K 2000 V – Spark Test AWG 20 : 5 kV .AWG 20 : 6 kV – Insulation resistance min. 20 MOhm x km – Minimum bending radius for permanent bending ca. 10 – 15 x core 1

1 – Bare copper fine wire ) stranded to DIN VDE 0295 cl. 5, BS 6360 cl. 5, HD 383 and IEC 60228 cl. 5 and UL-Subject 758 Section G – PVC core insulation TI3 to DIN VDE 0281 part 1 and UL-Std. 1581, class 43, CSA-C 22.2 No. 210 Tab. 12 class H – Core colours to DIN VDE 0293 – PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B), CSA FT1

Five norms approved connecting jumper wire primarily designed for exportes, used in machine tools. This wire is used for internal wiring of switchboards and electrical equipment. The approbation of HAR, UL-AWM, UL-MTW, CSA-AWM, CSA-Equipment-wire make possible an economical storekeeping and simplification of parts list.

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers **) Note AWG equivalet values – see page T 15. PVC cables will be changed to lead free PVC successively.

1

) Tinned conductor on request

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Type crosssec.

Outer 1

mm

Cop. weight kg/km

ca. RAL H05 V2-K/mm2 Part No. 0,5/AWG 20 2,5 Part No. 0,75/AWG 19 2,65 Part No. 1/AWG 18 2,8 H07 V2-K/mm2 Part No. 1,5/AWG 16 3,05 Part No. 2,5/AWG 14 3,6 Part No. 4/AWG 12 4,1 Part No. 6/AWG 10 4,8 Part No. 10/AWG 8 6,4 Part No. 16/AWG 6 8,1 Part No. 25/AWG 4 9,6 Part No. 35/AWG 2 10,8 H07 V-K/mm2 Part No. 50/AWG 1 13,6 Part No. 70/AWG 2/0 15,2 Part No. 95/AWG 3/0 16,8 Part No. 120/AWG 4/0 19,5 Part No. 150/300 kcmil 22,2

blackwhite

gn-ye

blue

brown

red

white

grey

viol.

yellow

pink

green

trans.

dark blue

orange

other colours

twintone

9005

6018/ 1021

5015

8003

3000

1013

7000

4005

1021

3015

6018



5010

2003





64075

64076

64077

64078

64079

64080

64081

64082

64083

64084

64085

64086

64087

64088

64089

64090

64091

64092

64093

64094

64095

64096

64097

64098

64099

64100

64101

64102

64103

64104

64105

64106

64107

64108

64109

64110

64111

64112

64113

64114

64115

64116

64117

64118

64119

64120

64121

64122

64123

64124

64125

64126

64127

64128

64129

64130

64131

64132

64133

64134

64135

64136

64137

64138

64139

64140

64141

64142

64143

64144

64145

64146

64147

64148

64149

64150

64151

64152

64153

64154

64155

64156

64157

64158

64159

64160

64161

64162

64163

64164

64165

64166

64167

64168

64169

64170

64171

64172

64173

64174

64175

64176

64177

64178

64179

64180

64181

64182

64183

64184

64185

64186

64187

64188

64189

64190

64191

64192

64193

64194

64195

64196

64197

64198

64199

64200

64201

64202

64203

64204

64205

64206

64207

64208

64209

64210

64211

64212

64213

64214

64215

64216

64217

64218

64219

64220

64221

64222

64223

64224

64225

64226

64227

64228

64229

64230

64231

64232

64233

64234

64235

64236

64237

64238

64239

64240

64241

64242

64243

64244

64245

64246

64247

64248

64249

64250

64251

64252

64253

64254

64255

64256

64257

64258

64259

64260

64261

64262

64263

64264

64265

64266

64267

64268

64269

64270

64271

64272

64273

64274

64275

64276

64277

64278

64279

64280

64281

64282

64283

64284

64285

64286

64287

64288

64289

64290

64291

64292

64293

64294

64295

64296

64297

64298

64299

64300

64301

64302

64303

64304

64305

64306

64307

64308

64309

64310

64311

64312

64313

64314

64315

64316

64317

64318

64319

64320

64321

64322

64323

64324

64325

64326

64327

64228

64329

64330

4,8 7,2 9,6

14,4 24,0 38,0 58,0 96,0 154,0 240,0 336,0

480,0 672,0 912,0 1152,0 1440,0

2

) The cross-sections 0,5, 0,75 and 1,0 mm2 are according to H05 V-K, the cross-sections 1,5 up to 35 mm2 according to H07 V-K, the cross-sections 435 mm2 are identified as H07V-K. Cross-sections up to 35 mm2 is according to DIN VDE 0281 part 5. Due to this cross-sections 435 mm2 is the type H07VK, but with an increased heat-resistant PVCcompound.

F4

â

THHN/THWN

908 C, 600 V UL listed PVC + Nylon-Single Cores

Technical data

Cable structure

Application

– PVC+Nylon insulated single cores as per UL-Styles and NEC standard – Temperature range as per Styles * THHN: 908 C dry – NEC standard * THWN: 758 C wet – NEC standard * AWM: UL-Styles 1316 to 1321 1058 C dry 808 C in oil * AWM: UL-Styles 1452, 1453 908 C dry 808 C in oil 1000 V * MTW: UL-Styles 1408 to 1414 908 C dry 808 C in oil 600 V – Nominal voltage 600 V – Test voltage (Spark test) AWG 14 to AWG 10 : 7,5 kV AWG 8 to AWG 2/0 : 10 kV AWG 3/0 to AWG 4/0 : 12,5 kV kcmil 250 to kcmil 500 : 15 kV kcmil 600 to kcmil 1000 : 17,5 kV

– Bare copper conductor, AWG-sizes as per given table below and ASTM B-3 and ASTM B-8 – Core insulation of PVC+Nylon-outer sheath – Cores colour coded, colour identification see below – Surface of jacket printed with markings: * 14 to 1000 MCM THHN (stranded) – (size) AWG TYPE MTW OR THHN OR THWN 600 V OR GASOLINE AND OIL RESISTANT II (UL) OR AWM E-51554 * 14 to 10 AWG THHN (solid) – (size) AWG TYPE THHN OR THWN 600 V OR GASOLINE AND OIL RESISTANT II (UL) OR AWM

As flexible connecting cable in machines, switch and distribution cabinets, cable assemblies and for fixed indoor installation, in tubes and in cable conduits.

Resistant against – Oils – Gasoline – Water – Acids – Ozone – Lyes – Sunlight – Abrasion

AWM: Appliance Wiring Material For internal wrings for electrical equipment and control apparatus e. g. radio and televisions, electronic assembly component MTW: Machine Tool Wire For the electronical installation of machine tools and the relative control THW: Thermoplastic PVC-insulated building wire, Heat resistant 758 C, for Wet and dry locations, flame retardant. THHN: Thermoplastic PVC-insulated building wire, Nylon jacketed, 908 C 600 V, for dry and damp locations. Normen = Underwriters Laboratories Inc. UL (USA)

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

PVC+Nylon-Single Cores, UL Listed Type THHN/THWN (908C) 600 V Part No.

AWGno.*)

crosssection mm2

conductor make-up AWGsize

n x wire 1

conductor 1 ca. mm

Wall-thickness (guiding value) PVCNyloninsulation jacket mm mm

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

DM / 100 m Cu 300, –

6320 6321 6322 6323 6324 6325

14 12 10 8 6 4

2,08 3,32 5,26 8,35 13,39 21,14

19/0,0147 19/0,0185 19/0,0234 19/0,0295 19/0,0378 19/0,0469

19 x 0,38 19 x 0,48 19 x 0,60 19 x 0,75 19 x 0,96 19 x 1,19

1,88 2,35 2,97 3,66 4,78 5,92

0,38 0,38 0,51 0,76 0,76 1,02

0,102 0,102 0,102 0,127 0,127 0,152

2,95 3,43 4,29 5,49 6,60 8,41

20,7 33,0 51,6 80,6 125,0 201,0

25 37 60 95 143 229

6326 6327 6328 6329 6330 6331 6332

3 2 1 1/0 2/0 3/0 4/0

26,65 33,61 42,38 53,47 67,40 84,97 107,17

19/0,053 19/0,0591 19/0,0664 19/0,0745 19/0,0837 19/0,094 19/0,1055

19 x 1,336 19 x 1,50 19 x 1,686 19 x 1,89 19 x 2,126 19 x 2,387 19 x 2,68

6,65 7,47 8,4 9,4 10,6 11,9 13,4

1,02 1,02 1,27 1,27 1,27 1,27 1,27

0,152 0,152 0,178 0,178 0,178 0,178 0,178

9,14 10,01 11,43 12,45 13,72 14,99 16,51

253,0 317,0 399,0 500,0 631,0 792,0 996,0

282 349 449 557 691 861 1069

63331 63341 63351 63361 63371 63381 63391 63401

250 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil 600 kcmil 750 kcmil 1000 kcmil

127 152 178 203 254 304 380 507

37/0,0822 37/0,0900 37/0,0973 37/0,104 37/0,1162 61/0,0992 61/0,1109 61/0,1280

37 x 2,088 37 x 2,286 37 x 2,47 37 x 2,7 37 x 2,95 61 x 2,52 61 x 2,82 61 x 3,25

14,6 16,0 17,3 18,9 20,7 22,7 25,3 29,3

1,52 1,52 1,52 1,52 1,52 1,78 1,79 1,78

0,203 0,203 0,203 0,203 0,203 0,229 0,229 0,229

18,29 19,56 21,08 22,35 24,13 26,75 29,36 33,27

1178,0 1410,0 1645,0 1902,0 2345,0 2920,0 3658,0 4858,0

1277 1515 1753 1998 2466 3000 3713 4796

1 kcmil = 1000 circ. mils = 0,5067 mm2. " You can find further information regarding UL/CSA-Cables on pages T 71 – T 77. Further types on request. Please complete the above part 0 green 5 1 black 6 2 blue 7 3 brown 8 4 red 9

no. for the colour required, using the following code: white grey yellow orange pink

Preis

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15. For further single cores see the following pages: – for PVC, see pages D 1 – D 10. – for PUR, see page G 32. – for rubber, see pages G 31, O 15. – halogen-free, see pages G 23 – G 24, E 5, E 15 – E 16, E 24 – E 26. – heat-resistant, see pages E 5 – E 6, E 10 – E 11, E 13 – E 16, E 21, E 23 – E 25. – vehicle cables, see pages K 1 – K 4. Further sizes and jacket colours available on request.

â

F5

F

â

HELUTHERM 145

UL/CSA approved, 300 V Single cores flexible, electron beam cross-linked, halogen-free

Technical data

Cable structure

Application

– Halogen-free single cores with increased heat resistance according to UL Style 3266 CSA CL 1252 – Temperature range flexing –358 C to +1208 C fixed installation –558 C to +1458 C in short circuit +2508 C – Nominal voltage U0/U 300/300 V – Test voltage 3500 V – Minimum bending radius approx. 4 x cable 1

– Tinned Cu wires, according to AWGsizes Conductor make-up: AWG 24 to AWG 14 19-wires AWG 12 65-wires AWG 10 105-wires – Core insulation of polyolefin-copolymer, electron beam cross-linked, flame retardant, halogen-free – Core colours see table below

These temperature resistant single-core cables are used for the internal wiring of lighting fixtures, heaters, electrical machinery, switching systems and distributors in equipment and plant and machinery, suitable for installation on, in and beneath plaster, in closed installation ducts, as well as for traffic systems and outdoor applications. These cables are not approved for direct routing on racks, gutters or tanks. For a protected installation, these cables may be used at a nominal voltage of up to 1000 V alternating current or a direct current up to 750 V when earthed. The maximum operating d.c. voltage used in rail vehicles shall not exceed 900 V when earthed. These halogen-free single core cables are characterised by their amazingly hight long-time resistance to temperature and feature among the leading halogen-free. Flame resistant products in the world. These single core cables singnificantly contribute to safety and the environment.

Tests – Flame test to DIN VDE 0482 part 266-2/ HD 405.3, BS 4066 part 3/EN 50266-2/ IEC 60332-3 (equivalent DIN VDE 0472 part 804 test method C) – Corrosiveness of combustion gases according to DIN VDE 0482 part 267/ EN 50267-2-2/IEC 60754-2 (equivalent DIN VDE 0472 part 813) – Halogen-free according to DIN VDE 0482 part 267/EN 50267-2-1/IEC 60754-1 (equivalent DIN VDE 0472 part 815) – Smoke density to VDE 0482 part 268-1 and 2, test method C, IEC 61034-1/ 61034-2, HD 606 and BS 7622 part 1 and 2 (DIN VDE 0472 part 816) – The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers – Caloric load values see page T 69

Advantages – Halogen-free, no liberation of corrosive or toxic vapours, in that way this helps saving valuable time when trying to evacuate a building in a diciplined manner and prevents unnecessary loss of life. – Lower propagation of fire – Low development of smoke and fumes – Good abrasion and notch resistance – Good resistance to oils and weathering – Resistant to UV radiation and ozone – Resistant to soldering temperatures – Thermal class B – These single-core cables are resistant to melting, even when in contact with a soldering iron at temperatures of between 3008 C and 3808 C, because of the electron-beam cross-linking for the insulation material. – Due to the high temperature profile the cross-section of conductor can under certain circumstances be reduced, hereby enabling a saving in space requirement and weight.

– Power ratings table see page T 27 = The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No. Crosssec. mm2

Part No. AWG 24 Part No. AWG 22 Part No. AWG 20 Part No. AWG 18 Part No. AWG 16 Part No. AWG 14 Part No. AWG 12 Part No. AWG 10

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

1,5

2,3

4

1,6

3,2

6

1,9

5,0

9

2,1

7,9

12

2,4

12,6

16

2,9

20,7

27

3,3

33,0

36

4,1

51,6

58

Preis DM%m Cu 300,gn/ye

Preis DM%m Cu 300,black

Preis DM%m light blue

Preis DM%m Cu 300,brown

Preis DM%m Cu 300,red

Preis DM%m Cu 300,white

Preis DM%m Cu 300,grey

Preis DM%m Cu 300,violet

Preis DM%m Cu 300,yellow

Preis DM%m Cu 300,orange

Preis DM%m Cu 300,green

Preis DM%m Cu 300,pink

Preis DM%m Cu 300,beige

Preis DM%m Cu 300,twintone

61816

61817

61818

61819

61820

61821

61822

61823

61824

61825

61826

61827

61828

61829

61830

61831

61832

61833

61834

61835

61836

61837

61838

61839

61840

61841

61842

61843

61844

61845

61846

61847

61848

61849

61850

61851

61852

61853

61854

61855

61856

61857

61858

61859

61860

61861

61862

61863

61864

61865

61866

61867

61868

61869

61870

61871

61872

61873

61874

61875

61876

61877

61878

61879

61880

61881

61882

61883

61884

61885

61886

61887

61888

61889

61890

61891

61892

61893

61894

61895

61896

61897

61898

61899

61900

61901

61902

61903

61904

61905

61906

61907

61908

61909

61910

61911

61912

61913

61914

61915

61916

61917

61918

61919

61920

61921

61922

61923

61924

61925

61926

61927

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15. For further single cores see the following pages: – for PVC, see pages D 1 – D 10. – for PUR, see page G 32. – for rubber, see pages G 33, O 15.

F6

– halogen-free, see pages G 23 – G 24, E 5, E 15 – E 16, E 24 – E 26. – heat-resistant, see pages E 5 – E 6, E 10 – E 11, E 13 – E 16, E 21, E 23 – E 25. – vehicle cables, see pages K 1 – K 4.

â

â

HELUTHERM 145

UL/CSA approved, 600 V Single cores flexible, electron beam cross-linked, halogen-free

Technical data

Cable structure

Application

– Halogen-free single cores with increased heat resistance according to UL Style 3271, CSA CL 1251 – Temperature range flexing –358 C to +1208 C fixed installation –558 C to +1458 C in short circuit +2508 C – Nominal voltage U 600 V – Test voltage 3500 V – Minimum bending radius approx. 4 x cable 1

– Tinned Cu wires, according to DIN VDE 0295 cl. 5, BS 6360 cl. 5 and IEC 60228 cl. 5 – Core insulation of polyolefin-copolymer, electron beam cross-linked, flame retardant, halogen-free – Core colours see table below

These temperature resistant single-core cables are used for the internal wiring of lighting fixtures, heaters, electrical machinery, switching systems and distributors in equipment and plant and machinery, suitable for installation on, in and beneath plaster, in closed installation ducts, as well as for traffic systems and outdoor applications. These cables are not approved for direct routing on racks, gutters or tanks. For a protected installation, these cables may be used at a nominal voltage of up to 1000 V alternating current or a direct current up to 750 V when earthed. The maximum operating d.c. voltage used in rail vehicles shall not exceed 900 V when earthed. These halogen-free single core cables are characterised by their amazingly hight long-time resistance to temperature and feature among the leading halogen-free. Flame resistant products in the world. These single core cables singnificantly contribute to safety and the environment.

Tests – Flame test to DIN VDE 0482 part 266-2/ HD 405.3, BS 4066 part 3/EN 50266-2/ IEC 60332-3 (equivalent DIN VDE 0472 part 804 test method C) – Corrosiveness of combustion gases according to DIN VDE 0482 part 267/ EN 50267-2-2/IEC 60754-2 (equivalent DIN VDE 0472 part 813) – Halogen-free according to DIN VDE 0482 part 267/EN 50267-2-1/IEC 60754-1 (equivalent DIN VDE 0472 part 815) – Smoke density to VDE 0482 part 268-1 and 2, test method C, IEC 61034-1/ 61034-2, HD 606 and BS 7622 part 1 and 2 (DIN VDE 0472 part 816) – The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers – Caloric load values see page T 69 – Power ratings table see page T 27

Advantages – Halogen-free, no liberation of corrosive or toxic vapours, in that way this helps saving valuable time when trying to evacuate a building in a diciplined manner and prevents unnecessary loss of life. – Lower propagation of fire – Low development of smoke and fumes – Good abrasion and notch resistance – Good resistance to oils and weathering – Resistant to UV radiation and ozone – Resistant to soldering temperatures – Thermal class B – These single-core cables are resistant to melting, even when in contact with a soldering iron at temperatures of between 3008 C and 3808 C, because of the electron-beam cross-linking for the insulation material. – Due to the high temperature profile the cross-section of conductor can under certain circumstances be reduced, hereby enabling a saving in space requirement and weight.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No. Crosssec. mm2

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

Part no. 0,25 2,3 2,4 7 Part no. 1 x 0,5 2,6 4,6 11 Part no. 1 x 0,75 2,8 7,2 14 Part no. 1 x 1,0 2,9 9,6 17 Part no. 1 x 1,5 3,2 14,4 22 Part no. 1 x 2,5 3,7 24,0 33 Part no. 1x4 4,2 38,4 53 Part no. 1x6 5,6 57,6 78 Part no. 1 x 10 7,5 96,0 136 Part no. 1 x 16 8,5 154,0 203 Part no. 1 x 25 10,4 240,0 300 Part no. 1 x 35 11,5 336,0 405 Part no. 1 x 50 14,4 480,0 580 For further single cores see the following pages: – for PVC, see pages D 1 – D 10. – for PUR, see page G 32.

Preis DM%m Cu 300,gn/ye

Preis DM%m Cu 300,black

Preis DM%m light blue

Preis DM%m Cu 300,brown

Preis DM%m Cu 300,red

Preis DM%m Cu 300,white

Preis DM%m Cu 300,grey

Preis DM%m Cu 300,violet

Preis DM%m Cu 300,yellow

Preis DM%m Cu 300,orange

Preis DM%m Cu 300,green

Preis DM%m Cu 300,pink

Preis DM%m Cu 300,beige

Preis DM%m Cu 300,twintone

59472

59473

59474

59475

59476

59477

59478

59479

59480

59481

59482

59483

59484

59485

59486

59487

59488

59489

59490

59491

59492

59493

59494

59495

59496

59497

59498

59499

59500

59501

59502

59503

59504

59505

59506

59507

59508

59509

59510

59511

59512

59513

59514

59515

59516

59517

59518

59519

59520

59521

59522

59523

59524

59525

59526

59527

59528

59529

59530

59531

59532

59533

59534

59535

59536

59537

59538

59539

59540

59541

59542

59543

59544

59545

59546

59547

59548

59549

59550

59551

59552

59553

59554

59555

59556

59557

59558

59559

59560

59561

59562

59563

59564

59565

59566

59567

59568

59569

59570

59571

59572

59573

59574

59575

59576

59577

59578

59579

59580

59581

59582

59583

59584

59585

59586

59587

59588

59589

59590

59591

59592

59593

59594

59595

59596

59597

59598

59599

59600

59601

59602

59603

59604

59605

59606

59607

59608

59609

59610

59611

59612

59613

59614

59615

59616

59617

59618

59619

59620

59621

59622

59623

59624

59625

59626

59627

59628

59629

59630

59631

59632

59633

59634

59635

59636

59637

59638

59639

59640

59641

59642

59643

59644

59645

59646

59647

59648

59649

59650

59651

59652

59653

– for rubber, see pages G 33, O 15. – halogen-free, see pages G 23 – G 24, E 5, E 15 – E 16, E 24 – E 26.

â

– heat-resistant, see pages E 5 – E 6, E 10 – E 11, E 13 – E 16, E 21, E 23 – E 25. – vehicle cables, see pages K 1 – K 4.

F7

F

Command Cable UL (LiYY)

approved Style 2464/300 V (808 C)

Technical data

Cable structure

Application

– Special PVC command cable, approved to UL-Style 2464, cores according AWG 26 – 20 to UL-Style 1061/1729 AWG 18 – 16 to UL-Style 1007/1569 – Temperature range –208 C to +808 C – Nominal voltage 300 V – Test voltage 1500 V – Breakdown voltage min. 3000 V – Minimum bending radius flexing approx. 15 x cable 1

– Tinned copper, fine wire conductors AWG 26 – 20 to ASTM-B 174-95 class J – M AWG 18 – 16 to ASTM-B 286 conductor make-up: to 0,14 mm2 = 7 x 0,162 mm 0,22 mm2 = 7 x 0,202 mm 0,34 mm2 = 7 x 0,254 mm 0,56 mm2 = 7 x 0,32 mm 0,82 mm2 = 19 x 0,235 mm 1,30 mm2 = 19 x 0,31 mm – Special PVC core insulation class 43, semirigid to UL-Std. 1581 table 50.182 and 50.183 – Colour coded to DIN 47100 – Cores stranded in layers with optimal lay-length – Special PVC outer jacket class 43 to UL-Std. 1581 table 50.182, colour * black * grey (preferred type for stock) – PVC flame retardant according to UL VW-1

Suitable for use as a command, measuring and control cable in tool making machinery conveyor system and production lines, in industrial plants and in air conditioning as well as in the steel producing industries. Resistance Conditionally resistant to – Oil – Solvents – Acids – Lyes – The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. strands

AWGno.*)

Size mm2

Outer 1 mm

83137 83138 83139 83140 83141 83142 83143 83144 83145 83146 83147

2 3 4 6 10 12 16 18 24 27 30

26 26 26 26 26 26 26 26 26 26 26

0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14

3,6 3,8 4,0 4,6 5,6 5,8 6,3 6,6 7,5 7,8 8,1

83153 83154 83155 83156 83157 83158 83159 83160 83161 83162 83163

2 3 4 6 10 12 16 18 24 27 30

24 24 24 24 24 24 24 24 24 24 24

0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22

83169 83170 83171 83172 83173 83174 83175 83176 83177 83178 83179

2 3 4 6 10 12 16 18 24 27 30

22 22 22 22 22 22 22 22 22 22 22

0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34

Weight ca. kg / km

Preis DM / 100 m Cu 300, –

Size mm2

Outer 1 mm

Weight ca. kg / km

Part No.

No. strands

AWGno.*)

13 15 18 25 38 46 56 62 82 97 110

83185 83186 83187 83188 83189 83190 83191 83192 83193 83194 83195

2 3 4 6 10 12 16 18 24 27 30

20 20 20 20 20 20 20 20 20 20 20

0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56

4,6 4,8 5,2 6,1 7,6 8,0 8,8 9,4 11,0 11,3 11,8

30 33 41 65 102 120 152 168 224 260 300

3,8 4,0 4,2 4,9 6,0 6,1 6,7 7,1 8,2 8,5 8,8

16 19 23 32 55 60 75 82 116 140 150

83201 83202 83203 83204 83205 83206 83207 83208 83209 83210 83211

2 3 4 6 10 12 16 18 24 27 30

18 18 18 18 18 18 18 18 18 18 18

0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82

6,1 6,4 6,9 8,1 10,4 10,9 12,2 13,0 15,2 15,8 16,3

50 62 72 100 180 182 240 270 370 400 470

4,2 4,3 4,6 5,5 6,8 7,0 7,8 8,3 9,6 10,0 10,2

25 30 45 60 80 105 130 140 190 207 225

83217 83218 83219 83220 83221 83222 83223 83224 83225 83226 83227

2 3 4 6 10 12 16 18 24 27 30

16 16 16 16 16 16 16 16 16 16 16

1,3 1,3 1,3 1,3 1,3 1,3 1,3 1,3 1,3 1,3 1,3

6,9 7,3 7,9 9,6 12,4 12,8 14,6 15,5 18,1 18,7 19,5

70 90 110 160 250 300 400 450 650 680 750

Preis DM / 100 m Cu 300, –

Continuation "

For further UL-approved control cables see the following pages: â – HELUKABEL JZ-602 page A 22 – A 23 â – HELUKABEL JZ-602-CY page A 26 – A 27 PVC cables will be changed to lead free PVC successively.

F8

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

â

Command Cable UL (LiYY)

approved, Style 2516/600 V (1058 C)

Technical data

Cable structure

Application

– Special PVC command cable, approved to UL-Style 2516 – Temperature range –208 C to +1058 C – Nominal voltage 600 V – Test voltage 2000 V – Breakdown voltage min. 4000 V – Minimum bending radius flexing approx. 15 x cable 1

– Tinned copper, fine wire conductors to ASTM-B 174, class J – K conductor make-up: to 2,08 mm2 = 41 x 0,254 mm 3,20 mm2 = 65 x 0,254 mm Special PVC core insulation class 43 to – UL-Std. 1581 table 50.182 (1058 C) – Colour coded to DIN 47100 – Cores stranded in layers with optimal lay-length – Special PVC outer jacket class 43 to UL-Std. 1581 table 50.182 (1058 C), colour * black * grey (preferred type for stock) – PVC flame retardant according to UL VW-1

Suitable for use as a command, measuring and control cable in tool making machinery conveyor system and production lines, in industrial plants and in air conditioning as well as in the steel producing industries. Resistance Conditionally resistant to – Oil – Solvents – Acids – Lyes

F

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers = The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. strands

AWGno.*)

83233 83234 83235 83236 83237 83238 83239 83240 83241 83242 83243 83244

2 3 4 6 10 12 16 18 24 27 30 36

14 14 14 14 14 14 14 14 14 14 14 14

Size mm2 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08

Outer 1 mm

Weight ca. kg / km

8,4 8,9 9,6 11,4 15,1 15,6 17,2 18,3 21,5 22,7 23,5 25,4

120 150 190 300 450 500 700 750 900 1100 1150 1800

For further UL-approved control cables see the following pages: â – HELUKABEL JZ-602 page A 22 – A 23 â – HELUKABEL JZ-602-CY page A 26 – A 27 PVC cables will be changed to lead free PVC successively.

Preis DM / 100 m Cu 300, –

Part No.

No. strands

AWGno.*)

83245 83246 83247 83248 83249 83250 83251 83252 83253

2 3 4 6 10 12 16 18 24

12 12 12 12 12 12 12 12 12

Size mm2 3,2 3,2 3,2 3,2 3,2 3,2 3,2 3,2 3,2

Outer 1 mm

Weight ca. kg / km

9,3 9,8 10,8 12,8 17,0 17,5 19,8 21,0 24,8

150 210 300 430 500 700 810 970 1200

Preis DM / 100 m Cu 300, –

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

â

F9

Command Cable UL (LiYCY)

approved and screen Style 2464/300 V (808 C) EMC*-preferred type

Technical data

Cable structure

Application

– Special PVC command cable, approved to UL-Style 2464, cores according AWG 26 – 20 to UL-Style 1061/1729 AWG 18 – 16 to UL-Style 1007/1569 – Temperature range –208 C to +808 C – Nominal voltage 300 V – Test voltage 1500 V – Breakdown voltage min. 3000 V – Minimum bending radius flexing approx. 15 x cable 1 – Coupling resistance max. 250 Ohm/km

– Tinned copper, fine wire conductors AWG 26 – 20 to ASTM-B 174-95 class J – M AWG 18 – 16 to ASTM-B 286 conductor make-up: to 0,14 mm2 = 7 x 0,162 mm 0,22 mm2 = 7 x 0,202 mm 0,34 mm2 = 7 x 0,254 mm 0,56 mm2 = 7 x 0,32 mm 0,82 mm2 = 19 x 0,235 mm 1,30 mm2 = 19 x 0,31 mm – Special PVC core insulation class 43, semirigid to UL-Std. 1581 table 50.182 and 50.183 – Colour coded to DIN 47100 – Cores stranded in layers with optimal lay-length – Seperator-foil – Drain wire – Tinned copper wire braiding, approx. 85% coverage

This cable type is suitable for use as a flexible connector cable in the fields of electronics, control and command technology as well as for measuring, signal and impulse transfer. Quick and cost favourable connections through cutting and clamping technics.

– Special PVC outer jacket class 43 to UL-Std. 1581 table 50.182, colour * black * grey (preferred type for stock) – PVC flame retardant according to UL VW-1

Resistance Conditionally resistant to – Oil – Solvents – Acids – Lye *EMC = Electromagnetic compatibillity Note To optimise the EMC features we recommend a large round contact of the cooper braiding on both ends. – The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. strands

AWGno.*)

Size mm2

Outer 1 mm

83254 83255 83256 83257 83258 83259 83260 83261 83262 83263 83264

2 3 4 6 10 12 16 18 24 27 30

26 26 26 26 26 26 26 26 26 26 26

0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14 0,14

3,9 4,2 4,4 5,0 6,1 6,3 6,8 7,1 8,0 8,4 8,6

83270 83271 83272 83273 83274 83275 83276 83277 83278 83279 83280

2 3 4 6 10 12 16 18 24 27 30

24 24 24 24 24 24 24 24 24 24 24

0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22 0,22

83286 83287 83288 83289 83290 83291 83292 83293 83294 83295 83296

2 3 4 6 10 12 16 18 24 27 30

22 22 22 22 22 22 22 22 22 22 22

0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34 0,34

Weight ca. kg / km

Preis DM / 100 m Cu 300, –

Size mm2

Outer 1 mm

Weight ca. kg / km

Part No.

No. strands

AWGno.*)

20 25 28 30 50 53 60 70 100 105 110

83302 83303 83304 83305 83306 83307 83308 83309 83310 83311 83312

2 3 4 6 10 12 16 18 24 27 30

20 20 20 20 20 20 20 20 20 20 20

0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56 0,56

5,1 5,3 5,6 6,6 8,1 8,4 9,5 9,9 11,5 12,0 12,4

30 40 50 70 110 130 160 180 240 260 300

4,2 4,4 4,7 5,3 6,5 6,7 7,3 7,6 8,7 9,0 9,5

20 25 30 40 60 70 90 100 120 130 150

83318 83319 83320 83321 83322 83323 83324 83325 83326 83327 83328

2 3 4 6 10 12 16 18 24 27 30

18 18 18 18 18 18 18 18 18 18 18

0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82

6,5 6,8 7,4 8,8 10,9 11,2 12,9 13,5 15,6 15,9 16,6

60 75 90 125 180 220 290 300 450 470 490

4,6 4,8 5,1 6,0 7,3 7,5 8,2 8,7 9,9 10,4 10,9

40 50 60 80 130 140 160 170 220 250 280

83334 83335 83336 83337 83338 83339 83340 83341 83342 83343 83344

2 3 4 6 10 12 16 18 24 27 30

16 16 16 16 16 16 16 16 16 16 16

1,30 1,30 1,30 1,30 1,30 1,30 1,30 1,30 1,30 1,30 1,30

7,0 7,4 8,1 9,5 12,4 12,8 14,0 14,8 17,2 18,0 18,7

90 160 200 290 450 600 650 680 900 990 1050

Preis DM / 100 m Cu 300, –

Continuation " For further UL-approved control cables see the following pages: â – HELUKABEL JZ-602 page A 22 – A 23 â – HELUKABEL JZ-602-CY page A 26 – A 27

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

PVC cables will be changed to lead free PVC successively.

F 10

â

Command Cable UL (LiYCY)

approved and screened Style 2516/600 V (1058 C) EMC*-preferred type

Technical data

Cable structure

Application

– Special PVC command cable, approved to UL-Style 2516 – cores according UL-Style 10012 – Temperature range –208 C to +1058 C – Nominal voltage 600 V – Test voltage 2000 V – Breakdown voltage min. 4000 V – Minimum bending radius flexing approx. 15 x cable 1 – Coupling resistance max. 250 Ohm/km

– Tinned copper, fine wire conductors to ASTM-B 174, class J – K conductor make-up: to 2,08 mm2 = 41 x 0,254 mm 3,20 mm2 = 65 x 0,254 mm Special PVC core insulation class 43 to – UL-Std. 1581 table 50.182 (1058 C) – Colour coded to DIN 47100 – Cores stranded in layers with optimal lay-length – Seperator-foil – Drain wire – Tinned copper wire braiding, approx. 85% coverage – Special PVC outer jacket class 43 to UL-Std. 1581 table 50.182 (1058 C), colour * black * grey (preferred type for stock) – PVC flame retardant according to UL VW-1

This cable type is suitable for use as a flexible connector cable in the fields of electronics, control and command technology as well as for measuring, signal and impulse transfer. Quick and cost favourable connections through cutting and clamping technics. Resistance Conditionally resistant to – Oil – Solvents – Acids – Lye *EMC = Electromagnetic compatibillity Note To optimise the EMC features we recommend a large round contact of the cooper braiding on both ends. – The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacqu

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. strands

AWGno.*)

83350 83351 83352 83353 83354 83355 83356 83357 83358 83359 83360

2 3 4 6 10 12 16 18 24 27 30

14 14 14 14 14 14 14 14 14 14 14

Size mm2 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08 2,08

Outer 1 mm

Weight ca. kg / km

8,4 9,4 10,1 11,9 15,7 16,2 17,9 18,8 22,6 23,3 24,1

180 220 270 380 600 770 870 990 1300 1400 1610

For further UL-approved control cables see the following pages: â – HELUKABEL JZ-602 page A 22 – A 23 â – HELUKABEL JZ-602-CY page A 26 – A 27

Preis DM / 100 m Cu 300, –

Part No.

No. strands

AWGno.*)

83362 83363 83364 83365 83366 83367 83368 83369 83370

2 3 4 6 10 12 16 18 24

12 12 12 12 12 12 12 12 12

Size mm2 3,2 3,2 3,2 3,2 3,2 3,2 3,2 3,2 3,2

Outer 1 mm

Weight ca. kg / km

9,9 10,3 11,2 14,0 17,6 18,1 20,0 22,1 25,3

200 240 300 400 580 800 900 1000 1300

Preis DM / 100 m Cu 300, –

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

PVC cables will be changed to lead free PVC successively.

â

F 11

F

Command Cable UL (LiYY-TP)

approved Style 2464/300 V (808 C)

Technical data

Cable structure

Application

– Special PVC command cable, approved to UL-Style 2464, cores according, UL-Style 1061/1729 – Temperature range flexing –108 C to +808 C fixed installation –208 C to +808 C – Nominal voltage 300 V – Test voltage 1500 V – Breakdown voltage min. 3000 V – Insulation resistance min. 100 MOhm x km – Minimum bending radius flexing approx. 15 x cable 1

– Tinned copper, fine wire conductors to ASTM-B 174-95 class J – M conductor make-up: to 0,14 mm2 = 7 x 0,162 mm 0,22 mm2 = 7 x 0,202 mm 0,34 mm2 = 7 x 0,254 mm 0,56 mm2 = 7 x 0,32 mm Special PVC core insulation class 43, – semirigid to UL-Std. 1581 table 50.182 and 50183 – Colour coded to DIN 47100 with colour repetition from pair no. 22 and above – Cores stranded in pains with optimal lay-length – Pains stranded in layers with optimal lay-length – Seperator-foil – Special PVC outer jacket class 43 to UL-Std. 1581 table 50.182, colour * black * grey (preferred type for stock) – PVC flame retardant according to UL VW-1

Twisted pair control cable for use in tool making machinery conveyor system and production lines, in industrial plants and in air conditioning as well as in the steel producing industries. Resistance Conditionally resistant to – Oil – Solvents – Acids – Lye

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part. No.

No. pairs x cross-sec mm2

AWGno.*)

83904 83905 83906 83907 83908 83909 83910 83911 83912 83913 83914 83915 83916 83917 83918 83919 83920 83921

1 x 2 x 0,14 2 x 2 x 0,14 3 x 2 x 0,14 4 x 2 x 0,14 5 x 2 x 0,14 6 x 2 x 0,14 7 x 2 x 0,14 8 x 2 x 0,14 10 x 2 x 0,14 12 x 2 x 0,14 14 x 2 x 0,14 15 x 2 x 0,14 16 x 2 x 0,14 18 x 2 x 0,14 20 x 2 x 0,14 22 x 2 x 0,14 24 x 2 x 0,14 25 x 2 x 0,14

26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26

83922 83923 83924 83925 83926 83927 83928 83929 83930 83931 83932 83933 83934 83935 83936 83937 83938 83939

1 x 2 x 0,22 2 x 2 x 0,22 3 x 2 x 0,22 4 x 2 x 0,22 5 x 2 x 0,22 6 x 2 x 0,22 7 x 2 x 0,22 8 x 2 x 0,22 10 x 2 x 0,22 12 x 2 x 0,22 14 x 2 x 0,22 15 x 2 x 0,22 16 x 2 x 0,22 18 x 2 x 0,22 20 x 2 x 0,22 22 x 2 x 0,22 24 x 2 x 0,22 25 x 2 x 0,22

24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24

Outer 1 ca. mm

Weight ca. kg / km

Part. No.

No. pairs x cross-sec mm2

AWGno.*)

3,6 5,1 5,3 5,8 6,2 6,8 6,8 7,3 7,4 9,1 9,8 10,6 10,6 11,1 11,9 12,4 13,1 13,4

20 24 30 38 44 51 57 64 76 93 103 109 112 119 130 150 169 178

83940 83941 83942 83943 83944 83945 83946 83947 83948 83949 83950 83951 83952 83953 83954 83955 83956 83957

1 x 2 x 0,34 2 x 2 x 0,34 3 x 2 x 0,34 4 x 2 x 0,34 5 x 2 x 0,34 6 x 2 x 0,34 7 x 2 x 0,34 8 x 2 x 0,34 10 x 2 x 0,34 12 x 2 x 0,34 14 x 2 x 0,34 15 x 2 x 0,34 16 x 2 x 0,34 18 x 2 x 0,34 20 x 2 x 0,34 22 x 2 x 0,34 24 x 2 x 0,34 25 x 2 x 0,34

22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22

4,2 5,9 6,3 7,0 7,6 8,2 8,2 9,0 10,7 11,3 12,1 12,7 12,7 13,6 14,4 15,1 16,2 16,7

38 44 60 79 92 119 128 139 171 194 222 231 240 264 291 300 359 381

3,8 5,4 5,7 6,2 6,6 7,2 7,2 7,8 9,2 9,7 10,2 10,9 10,9 11,5 12,2 13,0 13,7 14,2

32 36 48 56 71 80 89 98 111 135 160 171 185 209 230 248 279 292

83958 83959 83960 83961 83962 83963 83964 83965 83966 83967 83968 83969 83970 83971 83972 83973 83974 83975

1 x 2 x 0,56 2 x 2 x 0,56 3 x 2 x 0,56 4 x 2 x 0,56 5 x 2 x 0,56 6 x 2 x 0,56 7 x 2 x 0,56 8 x 2 x 0,56 10 x 2 x 0,56 12 x 2 x 0,56 14 x 2 x 0,56 15 x 2 x 0,56 16 x 2 x 0,56 18 x 2 x 0,56 20 x 2 x 0,56 22 x 2 x 0,56 24 x 2 x 0,56 25 x 2 x 0,56

20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

4,6 6,5 7,1 7,8 8,6 9,6 9,6 12,1 12,5 13,1 13,8 14,7 14,7 15,7 16,7 17,2 18,6 19,2

60 80 94 104 130 151 174 262 298 302 327 370 402 480 551 621 703 721

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

F 12

Outer 1 ca. mm

PVC cables will be changed to lead free PVC successively. Further jacket colours available on request.

â

Weight ca. kg / km

Command Cable UL (LiYCY-TP)

approved, Style 2464/300 V (808C), EMC*-preferred type, Cu-screened

Technical data

Cable structure

Application

– Special PVC command cable, approved to UL-Style 2464, cores according, UL-Style 1061/1729 – Temperature range flexing –108 C to +808 C fixed installation –208 C to +808 C – Nominal voltage 300 V – Test voltage 1500 V – Breakdown voltage min. 3000 V – Insulation resistance min. 100 MOhm x km – Minimum bending radius flexing approx. 20 x cable 1 – Coupling resistance max. 250 Ohm/km

– Tinned copper, fine wire conductors to ASTM-B 174-95 class J – M conductor make-up: to 0,14 mm2 = 7 x 0,162 mm 0,22 mm2 = 7 x 0,202 mm 0,34 mm2 = 7 x 0,254 mm 0,56 mm2 = 7 x 0,32 mm Special PVC core insulation class 43, – semirigid to UL-Std. 1581 table 50.182 and 50183 – Colour coded to DIN 47100 with colour repetition from pair no. 22 and above – Cores stranded in pains with optimal lay-length – Pains stranded in layers with optimal lay-length – Seperator-foil – Drain wire – Tinned copper wire braiding, approx. 85% coverage

Twisted pair control cable for use in tool making machinery conveyor system and production lines, in industrial plants and in air conditioning as well as in the steel producing industries.

– Special PVC outer jacket class 43 to UL-Std. 1581 table 50.182, colour * black * grey (preferred type for stock) – PVC flame retardant according to UL VW-1

Resistance Conditionally resistant to – Oils – Solvents – Acids – Lye *EMC = Electromagnetic compatibility Note To optimise the EMC features we recommend a large round contact of the copper braiding on both ends. – The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part. No.

No. pairs x cross-sec mm2

AWGno.*)

83774 83775 83776 83777 83778 83779 83780 83781 83782 83783 83784 83785 83786 83787 83788 83789 83790 83791

1 x 2 x 0,14 2 x 2 x 0,14 3 x 2 x 0,14 4 x 2 x 0,14 5 x 2 x 0,14 6 x 2 x 0,14 7 x 2 x 0,14 8 x 2 x 0,14 10 x 2 x 0,14 12 x 2 x 0,14 14 x 2 x 0,14 15 x 2 x 0,14 16 x 2 x 0,14 18 x 2 x 0,14 20 x 2 x 0,14 22 x 2 x 0,14 24 x 2 x 0,14 25 x 2 x 0,14

26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26

83792 83793 83794 83795 83796 83797 83798 83799 83800 83801 83802 83803 83804 83805 83806 83807 83808 83809

1 x 2 x 0,22 2 x 2 x 0,22 3 x 2 x 0,22 4 x 2 x 0,22 5 x 2 x 0,22 6 x 2 x 0,22 7 x 2 x 0,22 8 x 2 x 0,22 10 x 2 x 0,22 12 x 2 x 0,22 14 x 2 x 0,22 15 x 2 x 0,22 16 x 2 x 0,22 18 x 2 x 0,22 20 x 2 x 0,22 22 x 2 x 0,22 24 x 2 x 0,22 25 x 2 x 0,22

24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24

Outer 1 ca. mm

Weight ca. kg / km

Part. No.

No. pairs x cross-sec mm2

AWGno.*)

Outer 1 ca. mm

4,0 5,6 5,8 6,3 6,7 7,3 7,3 7,8 9,1 9,8 10,5 11,1 11,1 11,8 12,4 13,1 13,6 15,1

32 39 47 55 68 86 92 97 111 141 150 154 155 170 183 207 228 239

83810 83811 83812 83813 83814 83815 83816 83817 83818 83819 83820 83821 83822 83823 83824 83825 83826 83827

1 x 2 x 0,34 2 x 2 x 0,34 3 x 2 x 0,34 4 x 2 x 0,34 5 x 2 x 0,34 6 x 2 x 0,34 7 x 2 x 0,34 8 x 2 x 0,34 10 x 2 x 0,34 12 x 2 x 0,34 14 x 2 x 0,34 15 x 2 x 0,34 16 x 2 x 0,34 18 x 2 x 0,34 20 x 2 x 0,34 22 x 2 x 0,34 24 x 2 x 0,34 25 x 2 x 0,34

22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22

4,6 6,4 6,9 7,5 8,1 8,8 8,8 9,7 11,5 12,0 12,6 13,4 13,4 14,4 15,0 15,9 17,0 17,3

58 65 78 88 110 126 140 148 184 210 241 245 251 275 300 320 371 402

4,2 5,9 6,2 6,7 7,2 7,7 7,7 8,4 9,9 10,2 10,9 11,4 11,4 12,2 12,7 13,5 14,5 14,8

46 53 65 79 98 114 121 129 152 189 213 225 227 238 270 300 321 340

83828 83829 83830 83831 83832 83833 83834 83835 83836 83837 83838 83839 83840 83841 83842 83843 83844 83845

1 x 2 x 0,56 2 x 2 x 0,56 3 x 2 x 0,56 4 x 2 x 0,56 5 x 2 x 0,56 6 x 2 x 0,56 7 x 2 x 0,56 8 x 2 x 0,56 10 x 2 x 0,56 12 x 2 x 0,56 14 x 2 x 0,56 15 x 2 x 0,56 16 x 2 x 0,56 18 x 2 x 0,56 20 x 2 x 0,56 22 x 2 x 0,56 24 x 2 x 0,56 25 x 2 x 0,56

20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

5,0 7,0 7,6 8,3 9,1 10,1 10,1 12,7 13,2 13,6 14,4 15,5 15,5 16,3 17,1 18,0 19,4 19,8

70 89 102 119 140 162 198 272 307 318 342 381 417 494 570 643 724 740

Weight ca. kg / km

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15. PVC cables will be changed to lead free PVC successively. Further jacket colours available on request.

â

F 13

F

Rubber/Neoprene Control Cable UL-CSA approved; Types SJO and SO

Technical data

Cable structure

Application

– UL+CSA approved rubber/neoprene flexible cables – Temperature range SJO and SO –408 C to +908 C – Nominal voltage 300 volt for SJO – Nominal voltage 600 volt for SO – Approvals UL Subject 62 CSA-C22.2-49

– Plain copper conductors to ASTM B-174 – Core insulation of synthetic rubber, EPDM – Cores colour coded – Cores stranded in layers with optimal lay-length – Hemp or cotton tape – Outer jacket neoprene (oil resistant) – Jacket colour black

For use as a feeder cable under rough conditions in motors and machine construction, at shipyards, in steel production and in farming. Supply lengths are on original reels of 76 m or 152 m or on drums of 305 m lengths. Resistant – Oil – Wetness – UV-radiation

Colour code 2 cores = black, white 3 cores = black, white, green 4 cores = black, white, green, red = The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

Nominal voltage 300 volt, type SJO (908 C) Part No. type SJO

Neoprene sheath type SJO

AWG no.*) + Cores

Rating A

Stranding

Outer 1 ca. mm

63010 63011 63012 63013 63014 63015 63016 63017 63018

SJO-18/2 SJO-18/3 SJO-18/4 SJO-16/2 SJO-16/3 SJO-16/4 SJO-14/2 SJO-14/3 SJO-14/4

18/2 18/3 18/4 16/2 16/3 16/4 14/2 14/3 14/4

7 7 7 10 10 10 15 15 15

16 x 0,3 16 x 0,3 16 x 0,3 26 x 0,3 26 x 0,3 26 x 0,3 41 x 0,3 41 x 0,3 41 x 0,3

7,8 8,4 9,2 8,3 9,0 10,0 9,4 10,0 10,7

Rating A

Stranding

Outer 1 ca. mm

Weight ca. kg / km

Preis DM / 100 m Cu inkl.

65 80 95 130 148 180 195 225 288

Nominal voltage 600 volt, type SO (908C) Part No. type SO

Neoprene sheath type SO

AWG no.*) + Cores

63034 63035 63036 63037 63038 63039 63040 63041 63042 63043 63044 63045 63046 63047 63048

SO-18/2 SO-18/3 SO-18/4 SO-16/2 SO-16/3 SO-16/4 SO-14/2 SO-14/3 SO-14/4 SO-12/2 SO-12/3 SO-12/4 SO-10/2 SO-10/3 SO-10/4

18/2 18/3 18/4 16/2 16/3 16/4 14/2 14/3 14/4 12/2 12/3 12/4 10/2 10/3 10/4

7 7 7 10 10 10 15 15 15 20 20 20 25 25 25

16 x 0,3 16 x 0,3 16 x 0,3 26 x 0,3 26 x 0,3 26 x 0,3 41 x 0,3 41 x 0,3 41 x 0,3 65 x 0,3 65 x 0,3 65 x 0,3 105 x 0,3 105 x 0,3 105 x 0,3

10,0 10,4 11,0 10,4 11,0 12,3 13,5 14,3 15,3 15,3 16,2 18,9 16,4 17,5 19,0

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15. Further types also available: PVC control cables SJT, SJTO, ST, STO. Example: SJO-18/2 AWG 18

No. of cores

Further dimensions and versions available on request.

F 14

Weight ca. kg / km

n x AWG

â

70 86 110 140 155 200 200 235 300 280 310 330 305 325 365

Preis DM / 100 m Cu inkl.

PVC-Single Cores

to CEI 20-22 II

Technical data

Cable structure

Application

– PVC-Single Cores – As per Italian standard CEI 20 – 22 II – Temperature range flexing – 58 C to +808 C fixed installation –308 C to +808 C – Nominal voltage U0/U 450/750 V = 1 mm2 and above U0/U 300/500 V = 0,5 and 0,75 mm2 U0/U 300/300 V = 0,35 mm2 – Test voltage 2500 V – Minimum bending radius 4 – 6 x cable 1

– Bare fine wire stranded copper conductor to CEI 20 – 29 cl. 5 – PVC-core insulation R 2 up to CEI 20 II, cap. VI cl. 3 – Low smoke – PVC self-extinguishing and flame retardant

As hook up wire, control cabinet building, in cable assembly manufacturing as well as in electronic applications.

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Resistant to – Oil – Solvents – Acids – Lyes

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Type cross-sec.

Cop. weight kg / km

Outer 1 ca. mm

Weight ca. kg / km

Colour (per RAL) 05 V-K Part No. 0,35 mm2 Part No. 0,50 mm2 Part No. 0,75 mm2 07 V-K Part No. 1,0 mm2 Part No. 1,5 mm2 Part No. 2,5 mm2 Part No. 4,0 mm2 Part No. 6,0 mm2 Part No. 10,0 mm2 Part No. 16,0 mm2 Part No. 25,0 mm2 Part No. 35,0 mm2 Part No. 50,0 mm2 Part No. 70,0 mm2 Part No. 95,0 mm2 Part No. 120,0 mm2 Part No. 150,0 mm2

2,5

1,5

3,6

4,8

2,6

6,0

7,2

2,8

10,0

9,6

3,2

16,0

14,4

3,5

21,0

24,0

4,2

32,0

38,0

4,6

48,0

58,0

6,3

69,0

96,0

7,6

117,0

154,0

8,8

180,0

240,0

11,0

266,0

336,0

12,5

366,0

480,0

14,5

515,0

672,0

16,5

741,0

912,0

18,5

950,0

1152,0

21,0

1230,0

1440,0

23,0

1500,0

Preis DM%m Cu 300,black

Preis DM%m Cu 300,gn/ye

Preis DM%m Cu 300,blue

Preis DM%m Cu 300,brown

Preis DM%m Cu 300,red

Preis DM%m Cu 300,white

Preis DM%m Cu 300,dk.blue

Preis DM%m Cu 300,other colours

9005

6018/1021

5015

8003

3000

1013

5010

29600

29601

29602

29603

29604

29605

29606

29607

29608

29609

29610

29611

29612

29613

29614

29615

29616

29617

29618

29619

29620

29621

29622

29623

29624

29625

29626

29627

29628

29629

29630

29631

29632

29633

29634

29635

29636

29637

29638

29639

29640

29641

29642

29643

29644

29645

29646

29647

29648

29649

29650

29651

29652

29653

29654

29655

29656

29657

29658

29659

29660

29661

29662

29663

29664

29665

29666

29667

29668

29669

29670

29671

29672

29673

29674

29675

29676

29677

29678

29679

29680

29681

29682

29683

29684

29685

29686

29687

29688

29689

29690

29691

29692

29693

29694

29695

29696

29697

29698

29699

29700

29701

29702

29703

29704

29705

29706

29707

29708

29709

29710

29711

29712

29713

29714

29715

29716

29717

29718

29719

29720

29721

29722

29723

29724

29725

29726

29727

29728

29729

29730

29731

29732

29733

29734

29735

*) Note AWG equivalet values – see page T 15. PVC cables will be changed to lead free PVC successively. Further dimensions and versions on request. For further single cores see the following pages: – for PVC, see pages D 1 – D 10. – for PUR, see page G 34. – for rubber, see pages G 33, O 15. – halogen-free, see pages G 23 – G 24, E 5, E 15 – E 16, E 24 – E 26. – heat-resistant, see pages E 5 – E 6, E 10 – E 11, E 13 – E 16, E 21, E 23 – E 25. – vehicle cables, see pages K 1 – K 4.

Works photo: HELUKABELâ

â

F 15

F

FROR CEI 20-22 II

Technical data

Cable structure

Application

– Special PVC-sheathed flexible cord – As per Italian standard CEI 20 – 22 II – Temperature range flexing – 58 C to +708 C fixed installation –358 C to +708 C – Nominal voltage U0/U 300/500 V = 1 mm2 U0/U 450/750 V 1,5 mm2 and above – Test voltage 2000 V – Insulation resistance min. 20 MOhm x km – Radiation resistance up to 80 x 106 cJ/kg (80 Mrad) – Minimum bending radius approx. 10 x cable 1 – PVC self-extinguishing and flame retardant, test methods analog to IEC 60332-3

– Bare copper conductor, fine wire stranded to CEI 20 – 29 cl. 5 – Special PVC compound Mi R 2 – Colour coded up and to 4 cores to HELUKABEL-JB colour code see page T 48 – As of 5 cores black with continuous white number printing – Green-yellow earth core – Cores stranded in layers with optimal lay-length – Special PVC outer sheath – Sheath colour grey, similar to RAL 7035, with printing CEI 20 – 22 II – Oil- and petrol resistant as per CEI 20 – 22 II

Well known companies (FIAT, COMAU, etc.) use this cable for measurement and control purposes on machine tools and conveyors, as well as on production lines in equipment production and for special mechanical engineering. These cables are used for flexible use for medium mechanical stresses with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air. Due to special conductor insulation- and sheath compound, this cable is flame resistant in case of fire and self-extinguishing. The good oil- and petrol resistance allows the usage of this cable also in “problem“ areas.

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers = The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. cores x cross-sec. mm2

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

AWGno.*)

60250 60251 60252 60253 60254 60255 60256 60284 60285 60257 60258 60259

3G 1 4G 1 5G 1 7G 1 12G 1 18G 1 25G 1 27G 1 33G 1 34G 1 42G 1 50G 1

8,5 9,5 10,5 10,8 13,8 16,5 19,5 20,0 20,8 21,0 23,3 25,0

29 39 48 67 115 173 240 259 317 326 405 480

85 100 123 160 270 380 500 560 700 720 800 1050

17 17 17 17 17 17 17 17 17 17 17 17

60260 60261 60262 60263 60264 60265 60266 60267 60286 60268 60269

3G 1,5 4G 1,5 5G 1,5 7G 1,5 12G 1,5 18G 1,5 25G 1,5 34G 1,5 37G 1,5 42G 1,5 50G 1,5

9,6 11,0 12,0 12,5 16,0 18,8 23,0 26,0 26,5 29,5 30,5

43 58 72 101 173 259 360 490 533 605 720

105 150 190 220 350 515 705 990 1005 1080 1330

16 16 16 16 16 16 16 16 16 16 16

No. cores x cross-sec. mm2

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

AWGno.*)

60287 60270 60271 60272 60273

3G 2,5 4G 2,5 5G 2,5 7G 2,5 12G 2,5

11,3 12,3 12,6 14,5 18,0

72 96 120 168 288

190 215 270 350 550

14 14 14 14 14

60274 60275

4G 4 7G 4

14,0 16,0

154 269

300 500

12 12

60276 60277 60278 60279 60280 60281 60282 60283

4G 6 4G 10 4G 16 4G 25 4G 35 4G 50 4G 70 4G 95

16,0 19,0 23,0 28,0 31,0 37,0 43,0 50,0

230 384 614 960 1344 1920 2688 3648

430 700 1000 1550 2070 2850 4000 5400

10 8 6 4 2 1 2/0 3/0

Part No.

G = with green-yellow earth core X = without green-yellow earth core (OZ) *) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15. Further sizes available on request. Also available in screened version. PVC cables will be changed to lead free PVC successively.

F 16

â

C.N.O.M.O

type N05V V5-F according to NFC 32-206

Technical data

Cable structure

Application

– Special PVC based core insulation – As per to the french motor industry standard for tool machines 04-24-22 – Temperature range flexing – 58 C to +808 C fixed installation –308 C to +808 C – Nominal voltage 500 V – Test voltage 2000 V – Insulation resistance min. 20 MOhm x km – Radiation resistance up to 80 x 106 cJ/kg (80 Mrad) – Minimum bending radius 15 x cable 1

– – – –

Plain copper conductors Special core insulation Cores laid up Cores available in either red or black with white figure imprint – Green-yellow earth core – PVC outer jacket in blue or grey – PVC self-extinguishing and flame retardant, text method B and IEC 60332-1

These cables are constructed specially for the french automobile industries and used for the installation in tool making machines, production lines, industrial plants, air conditioning as well as for use in steel production. These cables are used for flexible use for medium mechanical stresses with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air. Resistant to – Oil – Petrol – Cutting oil according to C.N.O.M.O recommendation E 03.40.150N

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

F

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. cores x cross-sec. mm2

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

AWGno.*)

60000 OZ 60001 60002 60003 60004 60005 60006 60007 60008 60009 60010

2 x 0,75 3G 0,75 4G 0,75 5G 0,75 6G 0,75 12G 0,75 18G 0,75 27G 0,75 36G 0,75 48G 0,75 60G 0,75

6,2 6,6 7,2 8,0 8,9 11,6 13,9 17,2 19,7 22,8 24,9

14,4 21,6 29,0 36,0 50,0 86,0 144,0 230,0 288,0 360,0 439,0

50 59 72 87 105 175 267 404 503 670 805

18 18 18 18 18 18 18 18 18 18 18

60011 OZ 60012 60013 60014 60015 60016 60017 60018 60019 60020 60021

2x1 3G 1 4G 1 5G 1 6G 1 12G 1 18G 1 27G 1 36G 1 48G 1 60G 1

6,5 6,9 7,7 8,5 9,2 12,4 15,2 18,7 21,1 24,3 26,4

19,0 29,0 38,0 48,0 67,0 115,0 192,0 308,0 384,0 480,0 586,0

56 72 84 104 124 219 314 485 620 809 1000

17 17 17 17 17 17 17 17 17 17 17

No. cores x cross-sec. mm2

Outer 1 ca. mm

Cop. weight kg / km

60022 OZ 60023 60024 60025 60026 60027 60028 60029 60030 60031 60032 60033

2 x 1,5 3G 1,5 4G 1,5 5G 1,5 6G 1,5 12G 1,5 18G 1,5 24G 1,5 27G 1,5 36G 1,5 48G 1,5 60G 1,5

7,5 8,1 9,1 10,1 11,0 15,1 17,9 21,0 21,8 24,5 28,4 31,3

29,0 43,0 58,0 72,0 101,0 173,0 263,0 341,0 372,0 498,0 641,0 878,0

76 94 116 143 173 307 464 629 708 985 1175 1415

16 16 16 16 16 16 16 16 16 16 16 16

60034 OZ 60035 60036 60037 60038 60039

2 x 2,5 3G 2,5 4G 2,5 5G 2,5 6G 2,5 12G 2,5

10,5 11,0 12,0 13,1 15,0 18,0

48,0 72,0 96,0 120,0 168,0 288,0

122 151 191 244 292 524

14 14 14 14 14 14

60040 OZ 60041 60042 60043

2x4 3G 4 4G 4 5G 4

10,4 11,3 12,8 14,2

77,0 115,0 154,0 192,0

178 230 300 362

12 12 12 12

60044 OZ 60045 60046 60047

2x6 3G 6 4G 6 5G 6

11,6 12,7 14,2 15,7

115,0 173,0 230,0 288,0

218 325 481 584

10 10 10 10

60048 OZ 60049 60050 60051

2 x 10 3G 10 4G 10 5G 10

15,0 16,6 18,4 20,9

194,0 288,0 384,0 480,0

505 610 736 913

8 8 8 8

Part No.

Weight ca. kg / km

AWGno.*)

G = with green-yellow earth core X = without green-yellow earth core (OZ) *) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15. Further types and sizes available on request. OZ = Version without earth core. PVC cables will be changed to lead free PVC successively.

â

F 17

â

HELUKABEL JZ-604 TC TRAY CABLE PVC-Power Cable, UL/cUL-approved 908 C 600 V

Technical data

Cable structure

Application

– PVC power cable to UL-standard 1277 TRAY CABLE – Multinorm The TRAY CABLE also conforms to the following standards: (UL) MTW to UL-Std. 1063 AWM-Style 2587 to UL-Std. 758 (cUL) and CSA type TC FT4 to C22.2 no 230 CSA C22.2 No 210.2 I/II A/B 908C 600 V FT4 – Temperature range dry environment flexing – 58 C to +908 C fixed installation –258 C to +908 C wet environment flexing – 58 C to +758 C fixed installation –258 C to +758 C – Nominal voltage to UL 600 V – Test voltage 3000 V – Breakdown voltage min. 6000 V – Insulation resistance min. 20 MOhm x km – Minimum bending radius 7,5 x cable 1 – Radiation resistance up to 80 x 106 cJ/kg (up to 80 Mrad)

– Bare copper, fine wire conductors, according to DIN VDE 0295 cl. 5, BS 6360 cl. 5 and IEC 60228 cl. 5 – Special PVC core insulation class 12 B to table 50.155 UL-standard 1581, type TFF to UL-Std. 62 table 6.2 (AWG 20–AWG 16), type THHW to UL-Std. 83 table 5.2 ($ AWG 14) – Black cores with continuous white numbering according to DIN VDE 0293 – Green-yellow earth core in the outer layer (3 cores and above) – Cores stranded in layers with optimal lay-lengt – Special PVC outer sheath, Y 2400 to UL-Std.1277 table 11.18 Sheath colour black (RAL 9005) – Material self-extinguishing and flame retardant to UL-Standard 1277

UL-approved, flexible high current cables for use up to 600 V, for all machines, tools and installation work. Suitable for use in dry, damp and wet areas, outside, in cable ducts, open cable trays. Also inpipes, in the ground and for open installation in machinery and industrial areas.

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69661 69662 69663 69664 69665 69666 69667 69668 69669 69670 69671 69672

2x1 3G 1 4G 1 5G 1 7G 1 9G 1 10G 1 12G 1 18G 1 25G 1 34G 1 50G 1

18 18 18 18 18 18 18 18 18 18 18 18

8,0 8,4 9,1 10,0 11,7 12,6 14,3 14,7 17,1 20,3 23,7 26,1

19,2 29 39 48 67 84 96 115 173 240 326 480

74 87 99 117 151 172 206 260 371 481 551 959

69673 69674 69675 69676 69677 69678 69679 69680 69681 69682 69683 69684 69685 69686 69687 69688

2 x 1,5 3G 1,5 4G 1,5 5G 1,5 7G 1,5 8G 1,5 9G 1,5 10G 1,5 12G 1,5 16G 1,5 18G 1,5 25G 1,5 34G 1,5 41G 1,5 50G 1,5 61G 1,5

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

8,4 8,8 9,6 10,5 12,3 13,3 13,3 15,1 15,6 17,1 18,2 22,7 25,3 26,7 27,3 29,4

28,8 43 58 72 101 115 130 144 173 230 259 360 489 590 720 878

91 105 122 147 192 213 261 294 331 402 430 597 714 803 1021 1238

AWGno.*)

Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69689 69690 69691 69692 69693 69694 69695 69696 69697 69698 69699

2 x 2,5 3G 2,5 4G 2,5 5G 2,5 7G 2,5 8G 2,5 9G 2,5 10G 2,5 12G 2,5 18G 2,5 25G 2,5

14 14 14 14 14 14 14 14 14 14 14

9,4 9,9 10,8 11,8 14,7 16,0 16,0 17,1 17,7 20,8 25,8

48 72 96 120 168 192 216 240 288 432 600

111 140 161 194 257 339 341 392 470 682 891

69700 69701 69702 69703 69704 69705 69706

3G 4 4G 4 5G 4 7G 4 9G 4 12G 4 18G 4

12 12 12 12 12 12 12

11,0 12,0 13,2 16,5 17,8 19,9 24,2

115 154 192 269 346 461 691

190 229 284 394 480 841 981

69707 69708 69709 69710

3G 6 4G 6 5G 6 7G 6

10 10 10 10

12,5 14,5 15,8 17,3

173 230 288 403

290 384 468 654

69711 69712 69713 69714

3G 10 4G 10 5G 10 7G 10

8 8 8 8

16,9 18,6 20,4 23,5

288 384 480 672

511 587 784 970

AWGno.*)

Continuation "

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

F 18

G = with green-yellow earth core X = without green-yellow earth core (OZ) PVC cables will be changed to lead free PVC successively.

â

â

HELUKABEL JZ-604 TC TRAY CABLE PVC-Power Cable, UL/cUL-approbiert 908 C 600 V = The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69715 69716 69717 69718

3G 16 4G 16 5G 16 7G 16

6 6 6 6

21,0 23,9 26,3 28,8

461 614 768 1075

651 869 1117 1364

69719 69720 69721 69722

3G 25 4G 25 5G 25 7G 25

4 4 4 4

24,9 27,2 30,3 33,1

720 960 1200 1680

1090 1421 1611 1943

69723 69724 69725

3G 35 4G 35 5G 35

2 2 2

27,1 29,8 33,0

1008 1344 1680

1734 2011 2347

AWGno.*)

Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69726 69727 69728

3G 50 4G 50 5G 50

1 1 1

33,2 36,7 41,5

1440 1920 2400

2041 2539 2894

69729 69730 69731

3G 70 4G 70 5G 70

2/0 2/0 2/0

37,6 42,0 47,6

2016 2688 3360

2831 3494 4260

69732 69733 69734

3G 95 4G 95 5G 95

3/0 3/0 3/0

41,8 47,0 52,5

2736 3648 4560

5010 6104 7891

69735 69736 69737

3G 120 4G 120 5G 120

4/0 4/0 4/0

46,0 51,5 56,5

3456 4608 5760

5940 7604 8751

AWGno.*)

F

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

G = with green-yellow earth core X = without green-yellow earth core (OZ) PVC cables will be changed to lead free PVC successively.

â

F 19

â

HELUKABEL JZ-604-FCY TC TRAY CABLE PVC Power Cable screened, UL/cUL approved, 908C 600 V, EMC* preferred type

Technical data

Cable structure

Application

– PVC power cable, screened to UL-standard 1277 TRAY CABLE – Multinorm The TRAY-CABLE also conforms to the following standards: (UL) MTW to UL-Std. 1063 AWM-Style 2587 to UL-Std. 758 (cUL) and CSA type TC FT4 to C22.2 no 230, CSA C22.2 No 210.2 I/II A/B 908 C 600 V FT4 – Temperature range dry environment flexing – 58 C to +908 C fixed installation –258 C to +908 C wet environment flexing – 58 C to +758 C fixed installation –258 C to +758 C – Nominal voltage to UL 600 V – Test voltage 3000 V – Breakdown voltage min. 6000 V – Insulation resistance min. 20 MOhm x km – Minimum bending radius 10 x cable 1 – Radiation resistance up to 80 x 106 cJ/kg (up to 80 Mrad) – Coupling resistance max. 250 Ohm/km

– Bare copper, fine wire conductors,according to DIN VDE 0295 cl. 5, BS 6360 cl. 5 and IEC 60228 cl. 5 – Spezial PVC core insulation class 12 B to table 50.155 UL-standard 1581, type TFF to UL-Std. 62 table 6.2 (AWG 20–AWG 16), type THHW to UL-Std. 83 table 5.2 ($ AWG 14) – Black cores with continuous white numbering according to DIN VDE 0293 – Grenn-yellow earth core in the outer layer (3 cores and above) – Cores stranded in layers with optimal lay-lenght – Special separation foil – Tinned copper braided screening, approx. 85% coverage – Special PVC outer sheath, Y 2400 to UL-Std. 1277 table 11.18, – Sheath colour black (RAL 9005) – Material self-extinguishing and flame retardant to UL-Standard 1277

UL-approved, flexible high current cables for use up to 600 V, for all machines, tools and installation work. Suitable for use in dry, damp and wet areas, outside, in cable ducts, open cable trays. Also in pipes, in the ground and for open installation in machinery and industrial areas. *EMC = Electromagnetic compatibillity Note To optimise the EMC features we recommend a large round contact of the cooper braiding on both ends.

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69750 69751 69752 69753 69754 69755 69756 69757 69758 69759 69760 69761

2x1 3G 1 4G 1 5G 1 7G 1 9G 1 10G 1 12G 1 18G 1 25G 1 34G 1 50G 1

18 18 18 18 18 18 18 18 18 18 18 18

8,6 9,0 9,7 10,5 12,2 13,2 15,0 15,4 17,8 21,1 24,5 26,2

51,2 76,4 102,9 126,4 204,8 269,8 304,7 331,1 494,7 642,1 807,6 892,1

151 164 200 229 306 371 411 460 624 845 984 1096

69762 69763 69764 69765 69766 69767 69768 69769 69770 69771 69772 69773 69774 69775 69776 69777

2 x 1,5 3G 1,5 4G 1,5 5G 1,5 7G 1,5 8G 1,5 9G 1,5 10G 1,5 12G 1,5 16G 1,5 18G 1,5 25G 1,5 34G 1,5 41G 1,5 50G 1,5 61G 1,5

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

9,0 9,4 10,2 11,1 12,9 14,5 14,5 15,8 16,2 17,9 18,9 22,3 24,9 26,7 33,7 36,0

78,3 114,2 152,1 189,2 279,4 308,6 326,8 401,6 491,7 526,1 749,1 1011,4 1214,7 2060,6 3040,8 3416,1

161 181 240 274 367 431 437 511 598 630 787 1240 1401 2671 3614 4089

AWGno.*)

Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69778 69779 69780 69781 69782 69783 69784 69785 69786 69787 69788

2 x 2,5 3G 2,5 4G 2,5 5G 2,5 7G 2,5 8G 2,5 9G 2,5 10G 2,5 12G 2,5 18G 2,5 25G 2,5

14 14 14 14 14 14 14 14 14 14 14

10,0 10,5 11,4 12,4 15,3 16,5 16,5 17,9 18,4 22,4 26,5

128,4 189,5 250,1 314,2 464,3 490,9 498,6 511,6 764,1 1120,4 1714,0

269 294 341 420 551 583 593 631 847 1336 1921

69789 69790 69791 69792 69793 69794 69795

3G 4 4G 4 5G 4 7G 4 9G 4 12G 4 18G 4

12 12 12 12 12 12 12

11,6 12,6 14,5 17,1 18,4 20,5 25,0

304,2 402,7 514,2 721,2 849,3 1211,8 1714,9

381 504 692 908 1104 1497 2104

69796 69797 69798 69799

3G 6 4G 6 5G 6 7G 6

10 10 10 10

13,8 15,1 16,4 18,0

457,2 608,6 763,9 1002,8

623 729 1082 1414

69800 69801 69802 69803

3G 10 4G 10 5G 10 7G 10

8 8 8 8

17,6 19,3 22,1 24,2

796,7 1029,6 1273,8 1696,2

1108 1324 1596 2186

AWGno.*)

Continuation " *) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

F 20

G = with green-yellow earth core X = without green-yellow earth core (OZ) PVC cables will be changed to lead free PVC successively.

â

â

HELUKABEL JZ-604-YCY TC TRAY CABLE PVC Power Cable screened, UL/cUL approved, 908C 600 V, EMC* preferred type

Technical data

Cable structure

Application

– PVC power cable, screened to UL-standard 1277 TRAY CABLE – Multinorm The TRAY-CABLE also conforms to the following standards: (UL) MTW to UL-Std. 1063 AWM-Style 2587 to UL-Std. 758 (cUL) and CSA type TC FT4 to C22.2 no 230, CSA C22.2 No 210.2 I/II A/B 908 C 600 V FT4 – Temperature range dry environment flexing – 58 C to +908 C fixed installation –258 C to +908 C wet environment flexing – 58 C to +758 C fixed installation –258 C to +758 C – Nominal voltage to UL 600 V – Test voltage 3000 V – Breakdown voltage min. 6000 V – Insulation resistance min. 20 MOhm x km – Minimum bending radius 10 x cable 1 – Radiation resistance up to 80 x 106 cJ/kg (up to 80 Mrad) – Coupling resistance max. 250 Ohm/km

– Bare copper, fine wire conductors,according to DIN VDE 0295 cl. 5, BS 6360 cl. 5 and IEC 60228 cl. 5 – Spezial PVC core insulation class 12 B to table 50.155 UL-standard 1581, type TFF to UL-Std. 62 table 6.2 (AWG 20–AWG 16), type THHW to UL-Std. 83 table 5.2 ($ AWG 14) – Black cores with continuous white numbering according to DIN VDE 0293 – Grenn-yellow earth core in the outer layer (3 cores and above) – Cores stranded in layers with optimal lay-lenght – PVC-inner sheath, Y 2400 to UL-Std. 1277 table 11.18l – Tinned copper braided screening, approx. 85% coverage – Special PVC outer sheath, Y 2400 to UL-Std. 1277 table 11.18, – Sheath colour black (RAL 9005) – Material self-extinguishing and flame retardant to UL-Standard 1277

UL-approved, flexible high current cables for use up to 600 V, for all machines, tools and installation work. Suitable for use in dry, damp and wet areas, outside, in cable ducts, open cable trays. Also in pipes, in the ground and for open installation in machinery and industrial areas. *EMC = Electromagnetic compatibillity Note To optimise the EMC features we recommend a large round contact of the cooper braiding on both ends.

F

– The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC. Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69804 69805 69806 69807

3G 16 4G 16 5G 16 7G 16

6 6 6 6

25,2 27,8 31,2 34,5

1245,1 1655,2 2063,6 2886,5

1385 1861 2614 3211

69808 69809 69810 69811

3G 25 4G 25 5G 25 7G 25

4 4 4 4

29,0 32,4 34,2 40,3

1932,0 2561,1 3140,2 4481,7

2455 2721 3490 4960

69812 69813 69814

3G 35 4G 35 5G 35

2 2 2

32,4 36,2 40,5

2504,7 3320,8 4180,8

3130 4100 4921

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 – see page T 15.

AWGno.*)

Part No.

No. cores x cross-sec. mm2

AWGno.*)

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

69815 69816 69817

3G 50 4G 50 5G 50

1 1 1

40,4 45,5 50,0

3520,1 4821,7 5820,8

4560 5761 7186

69818 69819 69820

3G 70 4G 70 5G 70

2/0 2/0 2/0

47,1 51,1 56,0

5020,1 6620,3 8420,4

5580 7387 9290

69821 69822 69823

3G 95 4G 95 5G 95

3/0 3/0 3/0

50,1 55,0 60,5

6724,3 9100,0 10940,1

8520 10200 13800

69824 69825 69826

3G 120 4G 120 5G 120

4/0 4/0 4/0

54,0 59,5 64,5

8620,7 11420,0 12940,4

11090 13620 15420

AWGno.*)

G = with green-yellow earth core X = without green-yellow earth core (OZ) PVC cables will be changed to lead free PVC successively.

â

F 21