Download File

77 downloads 92107 Views 51KB Size Report
Application. Option CL18 is a two-stage thermostat and subbase with an auto/on fan (blower) ... the thermostat and the wiring diagram on the heater. Be sure to ...
Thermostat, Option CL18 Installation Form RZ-NA I-UD-T (Version A)

CERTIFIED

Obsoletes Form RZ-NA I-UD-T

APPLIES TO:

®

Description and Application

Kit Components

Models UDAP, UDAS, UDBP, and UDBS

Option CL18 is a two-stage thermostat and subbase with an auto/on fan (blower) switch and an off/auto system switch. It can be used with a two stage gas valve for two stages of heating control based on the temperature settings. Or, it can be used with a single-stage gas valve with the first stage control providing automatic fan or blower only recirculation operation and the second stage for heating. • If the application is two-stage heating, THESE INSTRUCTIONS DO NOT APPLY. Discard this sheet and the wiring diagram labels. Install the thermostat by following the manufacturer’s instructions that are provided with the thermostat and the wiring diagram on the heater. Be sure to comply with the requirements for thermostat location. • If the application is automatic thermostat controlled fan or blower only recirculation with a single-stage gas valve, follow the instructions on this sheet.

Option CL18 package, P/N 197265, includes: Qty

Two-Stage Thermostat with Subbase

P/N

Description

1

93436 Two-Stage Thermostat, Honeywell #T874F1130, with Subbase, Honeywell #Q674C1009

1

197138 Wiring Diagram Label for UDAP or UDAS

1

197141 Wiring Diagram Label for UDBP or UDBS 30-125 with direct drive motor

1

202648 Wiring Diagram Label for UDBP or UDBS 150-400 with contactor (AN2), 115/1, 208/1, 230/1, 208/3 or 230/3volt supply (AK 1, 2, 3, 5, or 6)

1

202649 Wiring Diagram Label for UDBP or UDBS 150-400 with a starter (AN10), 115/1, 208/1, 230/1, 208/3 or 230/3volt supply (AK 1, 2, 3, 5, or 6)

1

202650 Wiring Diagram Label for UDBP or UDBS 150-400 with contactor (AN2), 460/3 volt supply (AK7)

1

202651 Wiring Diagram Label for UDBP or UDBS 150-400 wit h a starter (AN10), 460/3 volt supply (AK 7)

1

203174 Wiring Diagram Label for UDBP or UDBS 150-400 wit h a starter (AN10), 575/3 volt supply (AK8)

Installation Instructions for Automatic Fan or Blower Only Recirculation Control and Single-Stage Heating

WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment. 1. Install the Thermostat Install the thermostat according to the manufacturer’s instructions. Be careful to comply with the requirements covering the location of the thermostat. Follow connection diagram in FIGURE 1 on page 2 to connect the 24 volt thermostat wiring. Form RZ-NA I-UD-T, P/N 197264, page 1

Installation Instructions (cont’d) FIGURE 1 - 24 Volt Connections for Model UDAP, UDAS, UDBP, or UDBS with Single-Stage Gas Valve and Option CL18 Two-Stage Thermostat TERMINAL STRIP ON BACK OF HEATER

FACTORY WIRING FIELD WIRING

W1 PR

P3-1

Y

P3-2

G Q674C SUBBASE

(OPT CL18) T874F THERMOSTAT

G

W1 W2

RC

P3-3

DOOR INTERLOCK (UDBS ONLY)

R

R

R

P3-4

Y

G

INTEGRATED CIRCUIT BOARD

W

R

RH

W2

Set thermostat second stage anticipator at 0.6 amps and first stage anticipator at minimum. Jumper thermostat terminals G to W1 and RH to RC.

2. Adhere the New Wiring Diagram Label Select the appropriate wiring diagram label from the package. (Only one will be used; discard the other wiring diagram labels.) Before removing the backing, position the wiring diagram label over the wiring diagram on the heater. Carefully remove the backing and adhere the label so that it completely covers the wiring diagram already on the heater. 3. For future reference, put this instruction sheet with the heater installation manual. Turn on the electric and the gas. Follow the lighting instructions to light the heater. Check for proper operation.

(800) 695-1901; www.ReznorOnLine.com ©2002 Thomas & Betts Corporation, All rights reserved. Printed in the U.S.A. MANUFACTURER OF HEATING, COOLING, AND VENTILATING SYSTEMS Trademark Note: Reznor® , TCORE2® , and Form RZ-NA I-UD-T, P/N 197264, page 2

8/02 Form RZ-NA I-UD-T (Version A)