Phase Sequence Signalling Relay - BRP0103 - Midland Jay

80 downloads 56 Views 77KB Size Report
P.O.Box 395, Huddersfield, HD1 9YR, England. Telephone: +44 (0)1484 461133 Fax: +44 (0)1484 461123. Website: www.midlandjay.co.uk Email: ...
P.O.Box 395, Huddersfield, HD1 9YR, England Telephone: +44 (0)1484 461133 Fax: +44 (0)1484 461123 Website: www.midlandjay.co.uk Email: [email protected]

Phase Sequence Signalling Relay - BRP0103

When all three phases are present with a forward phase sequence the output relay will energise. In the event of a negative phase sequence or supply / phase failure the output relay will not energise. Please note, this unit is intended for phase sequence signalling only and not for use as a phase failure relay. Supply to the unit should be via either 1 amp H.R.C. fuses or a 1 amp M.C.B.

Supply Voltage:

415Vac 3 phase

Voltage tolerance:

-20% +10%

Frequency:

50 Hz

Phase rotation:

Sensitive

Relay contacts:

Single-pole changeover

Contact rating:

250Vac 3A ((cos cosφ > 0.4)

Isolation voltage:

2kV ac for 1 minute

Power consumption:

Less than 5VA

Temperature range:

-10° -10°C to +60° +60°C

Construction:

Din rail mounted housing to IP20

Weight:

0.35Kg

45

120

L1 L2 L3

11

L1 L2 L3 21 11 BRP****

74

The BRP0103 is a phase sequence signalling relay. The unit provides a positive indication of a forward phase sequence.

tectrite

MIDLAND JAY

12

14

22 24 12 14

MOUNTING RAIL - DIN46277Pt.3

BRP0103/03/07