In cases when a DKO or DKW is used as replacement of a TF- or TTO/MMO-
control box, ... Satronic AG ... and its wiring is according to the diagram DKW 976.
130/12/00
A Honeywell Company
Cross reference list
for oilburners old type (no longer available)
new type Type
remarks Item-No
IBR 661
TME 780
08801
New wiring incl.new base necessary. change flame detector (replacement: FZE 780)
OBR 661 BR 661
TMO 720-4
08001
New wiring incl.new base necessary. change flame detector (replacement: FZ 711S)
KBR 6xx TF 2x
TF 830 or TF 832
02001 02404
New wiring incl.new base necessary. change flame detector (replacement: MZ 770S)
TF 701 TF 701-1 TF 714-1
TF 801 (1-stage) or TF 802 (2-stage)
02001 02404
TF 704
TF 804
02005
TF 721
TF 830 (1-stage) or TF 832 (2-stage)
02201 02401
The different diameter of the photocells can be compensated by an adapter (FZ/MZ) or by using the MZ-mounting flange (Art.Nr. 59101)
change flame detector (replacement: MZ 770S) The different diameter of the photocells can be compensated by an adapter (FZ/MZ) or by using the MZ-mounting flange (Art.Nr. 59101) change flame detector (replacement: MZ 770S) The different diameter of the photocells can be compensated by an adapter (FZ/MZ) or by using the MZ-mounting flange (Art.Nr. 59101)
General remarks The overall height difference can be compensated with the reset button extension (Item-No. 70601) In cases when a DKO or DKW is used as replacement of a TF- or TTO/MMO- control box, we recommend to replace the base with the type S98 (Item-No 75300 or 75310). Generally, program sequence and functions of the new control boxes correspond to those of the replaced control boxes. Due to their design, minor differences can occur with certain applications. 1
for oilburners old type (no longer available)
new type Type
remarks Item-No
TTO 750-1 TTO 810
DKW 972 Mod.05
0322005
change flame detector (replacement: MZ 770S, IRD 1010, UVD 970) and its wiring is according to the diagram DKW 972. Make sure that terminal 1 is not connected to live.
TTO 872 MMO 872
DKW 972 Mod.05
0322005
Flame detector IRD 1010 or UVD 970. Its wiring is according to the diagram DKW 972.
TTO 836
DKW 976 Mod.05
0326005
change flame detector (replacement: MZ 770S, IRD 1010, UVD 970) and its wiring is according to the diagram DKW 976.
TTO 876 MMO 876
DKW 976 Mod.05
0326005
Flame detector IRD 1010 or UVD 970 Its wiring is according to the diagram DKW 976.
MMD 880 MMD 900
DKO 972 Mod.25
0312025
Certified only for compressed air burners system Satronair.
MMD 900.1
DKO 972 Mod.22
0312025
Certified only with flame detector MZ 770S, IRD 1010, UVD 970.
General remarks The overall height difference can be compensated with the reset button extension (Item-No. 70601) In cases when a DKO or DKW is used as replacement of a TF- or TTO/MMO- control box, we recommend to replace the base with the type S98 (Item-No 75300 or 75310). Generally, program sequence and functions of the new control boxes correspond to those of the replaced control boxes. Due to their design, minor differences can occur with certain applications.
Cross reference list
A Honeywell Company
2
Satronic AG Honeywell-Platz 1 Postfach 324 CH-8157 Dielsdorf