DD, MPX. Selection. Answering. Machine. Bypass. Ground. Start Relay. Relay Output 2. Use Model 305. Command. Processor. Reset. J16. Battery. Only. Restart.
Model XR200 Wiring Diagram

Refer to the XR200 Installation Guide (LT-0197) for a complete description of wiring connections. Refer to the XR200 Programming Guide (LT-0196) for complete programming instructions.

Battery Only Restart CR7

J2 Output Color Code for Model 430 Harness

J10

Cold Water

s

s

s

s

Bell

11

12

13

15

14

16

19

1k 1k Ohm Ohm

17

18

1k 1k Ohm Ohm

s = Supervised Circuit s

20

21

1k 1k Ohm Ohm

Z7 GND Z8 22

23 Zone 7

10

Zone 5

9

Zone 6

8

Z5 GND Z6

Zone 3

Maximum AC Wire distance s with 16 gauge wire: 70 feet s with 18 gauge wire: 40 feet RED BLACK

7

Zone 1

6

Z3 GND Z4

Zone 2

5

22 gauge minimum

4

22 gauge minimum

3

BLACK

2

22 gauge minimum

1

-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2

GREEN

+B

22 gauge minimum

AC

RED

AC

K6 K7

J16 Command Processor Reset

Relay Output 2 Use Model 305

Zone 4

Relay Output 1 Use Model 305

YELLOW

16 to 18 s gauge wire

Secondary Power Supply 1.2 Amps Max. charging current. Use only 12 VDC rechargeable batteries. DMP Model 367. Replace every 3 to 5 years.

Wiring on terminals 5 through 22 must exit right and maintain a 1/4" separation from the AC and battery positive wiring.

Output Header J2

Bell 12 VDC Total current 1.5 Amps Max. Minimum cutoff time is 5 minutes.

Keypads Models 690/690F 77mA at 12 VDC Models 790/790F/791 77mA at 12 VDC Model 693/793 92mA at 12 VDC Model 630F 63mA at 12 VDC Model 7060 80mA at 12 VDC Model 7070 72mA at 12 VDC Models 7063 86mA at 12 VDC Models 7073 93mA at 12 VDC

Tamper Header J4

Answering Ground Machine K2 K4 Start Relay Bypass

Plug into 120 VAC 60 Hz outlet not controlled by switch. s

Form C Relays Output 1 N/C Violet Output 1 Com Gray Output 1 N/O Orange Output 2 N/C Violet Output 2 Com Gray Output 2 N/O Orange Voltage Outputs Output 3 White/Orange Output 4 White/Yellow Output 5 White/Green Output 6 White/Blue Output 7 White/Violet Output 8 White/Gray Output 9 White Output 10 White/Black Ground Black

AC Wiring must be in conduit and exit out the left side of the enclosure.

J12 J11

Phone Jack

24

ARMED

ARM 1k Ohm 1k Ohm 1k Ohm

25 26

27 28

Zone 9

Zone 10

3.3k

3.3k

Rear Heat detectors, pull stations, or any other contact devices listed for Fire Protective Signaling can be Zones 9 and 10 and Model 715 compatibility identifier: A Maximum operating range: 8.8 VDC to 14.2 VDC. Class B (Style A).

Auxiliary Power Ohm Ohm Resistor Resistor Total current 1.0 Amps combined from terminals 7, 11, 26, and 28. Verification Control Unit Smoke Detector 10.2 VDC to 14.0 VDC Zones Delay Model Delay ______ 13.6 sec. ______ ____sec. RED The use of verification delays on zones 9 and 10 is optional. Use the delays marked on the smoke Zone Expander Model 715 7mA @ 12 VDC Models 715-8, 715-16 20mA @ 12 VDC

GREEN BLACK

DISARM

Z9+ Z9- Z10+ Z10-

Front

1k 1k Ohm Ohm

RED YELLOW

POWER

Tamper protection when required for Model 350A Attack Resistant Enclosure.

s

DD, MPX Selection

J3

Keyswitch Arming can be connected to any zone. See LT-0197 Section 10.4. DMP Transformers Model 320 16.5 VAC 40 VA Class 2 wire-in. Model 321 16.5 VAC 40 VA Class 2 plug-in. Model 322 16.5 VAC 56 VA Class 2 wire-in.

POWER LIMITED All circuits on the Model XR200 comply with the requirements for inherent power limitation and are Class 2 except the red battery wire. s

See section 11.2 in the XR200 Installation Guide (LT-0197) for a list of approved 2-wire smoke detectors for zones 9 and 10, and 715 and 725 zone expanders. See LT-0164 for a list of approved 4-wire smoke detectors and power supervision relays.

HOUSEHOLD FIRE WIRING UL recognized limited energy cable must be used for connection of all initiating, indicating, and supplementary devices.

Zone 8

Suitable for Remote Station Signaling Service with DMP Model 893 DACT. Also suitable for use with Radionics D127 Module. See LT-0197 sections 23.9 and 25.5. Suitable for manual fire alarm, automatic fire alarm, sprinkler supervisory, or water flow alarm UL Listed Resistors 1.0k Ohm - DMP Model 311 3.3k Ohm - DMP Model 309 10K Ohm - DMP Model 308

NFPA 72 OPERATING INSTRUCTIONS The operating instructions sheet (LT-0352 and in the back of LT-0197) must be attached to the control unit or framed and located adjacent to the control unit or keypad.

NFPA 72 This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72-1993, (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided with this equipment.

Types of Service Central Station DACT, MUX, Type 1, 2, and 3 signaling service may be provided. See LT-0197 sections 23.4 to 23.6.

Smoke Detector

Use UL Listed Power Supervision Relay rated at 12 VDC.

Zone Expander Model 714 7mA @ 12 VDC Models 714-8, 714-16 20mA @ 12 VDC

1k Ohm 1k Ohm 1k Ohm

1k Ohm

WARNING THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM VERIFICATION FEATURE THAT RESULTS IN DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS. NOT OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

Zone Expander Model 711 7mA @ 12 VDC

1k Ohm

3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm

Zones 9, 10, and all expanded zones are suitable for installations as Class B (as applicable for the initiating and signaling line circuits per UL 864 Table 48.2 or 48.3), central Station Type 1, Type 2, or Type 3 multiplex system. Installation limits under Jurisdiction of local authority.

In all applications where more than one wire is under a terminal, the wire must be cut, and not looped around the screw terminal.

LT-0204 (12/06) © 2006 Digital Monitoring Products, Inc.