Power Quality Disturbance Detection in Grid-Connected Wind Energy System Using Wavelet and S-Transform Prakash K. Ray, Harish C. Dubey, Soumya R. Mohanty, Nand Kishor, and K. Ganesh

Abstract: S-transform and wavelet transform based approach for detection of different power quality disturbances like voltage sag, voltage swell, momentary interruption, notch and oscillatory transients in gridconnected wind power system is proposed in this paper. The voltage signal at point of common coupling is used in detection of the disturbances. The excellent time-frequency resolution characteristic of S-transform is exploited for detecting various power quality disturbances. The simulated results clearly reflect the advantages of S-transform over wavelet transform in localizing and detecting the power quality events even under noisy conditions. Index terms: Power quality, S-transform, wavelet transform, wind energy system.

I. INTRODUCTION istributed generation (DG) has recently gained momentum and popularity due to market deregulation and awareness for clean environments [1]-[2]. In fact, many utilities around the world already have a significant penetration of DG in their system. But there are many issues to be seriously considered with the DG connected to utility grid and one of the main issues is power quality. Power quality disturbances occur due to the presence of power electronics based non-linear loads, unbalance in power system, computer and data processing equipments etc. at the point of common coupling (PCC). If not detected effectively, these power quality disturbances may lead to many problems to the generators and connected loads [3]. It is desired to know the sources of power system disturbances and find remedies to mitigate them. In this context, wavelet transform [4]-[5] is an attractive and

D

effective candidate for detecting various power quality disturbances. Wavelet transform is useful in detecting and extracting disturbance features of disturbances because it is sensitive to signal irregularities but insensitive to the regular signal behavior. But the major drawback of wavelet transform is its batch processing step, which results to introduction of delay. An alternative and extension to wavelet transform is the S-transform [6]-[7], which is based on moving a varying and scalable localizing Gaussian window and is fully convertible from the time domain to two-dimensional (2-D) frequency translation domain. The S-transform has an advantage of providing multi-resolution while retaining the absolute phase of each frequency component which is useful in detecting the disturbances in presence of noise. The phase correction of the modified wavelet transform in the form of S-transform can provide significant improvement in the detection and localization of power quality disturbances. Any abrupt change occurred in the acquired signal would be effectively caught, hence increasing the reliability of detection. II. GRID-CONNECTED WIND ENERGY CONVERSION SYSTEM (WECS) The wind power which has been expected to be a promising alternative energy source can bring new challenges when it is connected to the power grid due to the fluctuation nature of the wind and the comparatively new types of its generators. However, to obtain secure and reliable operation, several technical issues related to power quality are required to be critically studied. Non-linear Load

DFIG Transformer 1 MVA

Prakash K. Ray, Soumya R. Mohanty , Nand Kishor, and K. Ganesh are with the Electrical Engineering Department, Motilal Nehru National Institute of Technology, Allahabad, India (Ph : +91-945-500-6918 ; e-mail: [email protected], [email protected] & [email protected], [email protected] ). Harish C. Dubey is an Undergraduate Research Student in the Electronic & Communications Engineering Department, Motilal Nehru National Institute of Technology, Allahabad, India (e-mail: [email protected]).

wind

CB2

CB 1 capacitor

Gear box

Linear Load

blades

GRID

PCC rotor side converter

grid side converter

Fig.1 Configuration of grid-connected wind energy conversion system.

Fig. 1 shows a model of grid-connected wind energy conversion system considered in the study of power quality disturbances detection.

978-1-4244-8541-3/10/$26.00 ©2010 IEEE

2 A. Wind energy conversion system (WECS) In general, the relationship between wind speed and mechanical power extracted from the wind can be described as [8] Pm

2

Awt C p ( ,

)Vw3

(1) where Pm is the power extracted from the wind in watts; ρ is the air density (kg/m3); Cp is the performance coefficient or power coefficient; λ is the tip-speed ratio (Vt/Vw), Vt (m/s) is blade tip speed, and Vw (m/s) is wind speed at hub height upstream of the rotor;

Awt

R 2 is the area covered by

the wind turbine rotor (m2), R is the radius of the rotor; and β is the blade pitch angle (in degrees). R r The tip-speed ratio λ is defined as : where vw r

p

m

r

is the electrical speed (elec. rad/s); p is the

number of pole pairs of the machine; and

m is

the

mechanical speed of the rotor (mech. rad/s). The doubly-fed induction generator (DFIG) model used as a part of the WECS is taken from [9]. III. POWER QUALITY DISTURBANCE DETECTION METHODS A. Discrete Wavelet transforms (DWT) In this study, the voltage signals at PCC are used as the input signals of the wavelet analysis. Haar mother wavelet, is employed since it has been demonstrated to perform well [4]-[5]. Filters of different cut-off frequencies are used to analyze the signal at different scales. The signal is passed through a series of high pass filters to analyze the high frequencies, and it is passed through a series of low pass filters to analyze the low frequencies. Hence the signal (S) is decomposed into two types of components approximation (A) and detail (D). The approximation (A) is the high scale, low-frequency component of the signal. The detail (D) is the low-scale, high-frequency components. The first-scale decomposition of a digitized time signal is C0 (n) in terms of approximation and detailed version are given by a1 (n)

h(k 2n) C0 (k ) and k

d1 (n)

g (k 2n) C0 (k )

(2)

k

where, h(n) has a low-pass filter response and

g (n)

has a high-pass filter response. The next higher scale decomposition is based on a1 (n) instead of C0 (n) . At each scale, the number of the DWT

coefficients of the resulting signals (e.g. a1 ( n ) & d1 ( n ) ) is half of the decomposed signal (e.g. C0 ( n) ). B. Modified Wavelet Transform: S–Transform It is well known that information is contained in the phase of the spectrum, as well as in the amplitude. In order to utilize the information contained in the phase of the continuous wavelet transform (CWT), it is necessary to modify the phase of the mother wavelet. The CWT W ( , a) of

a

function

W ( , a)

h(t )

is

h(t )

(t

defined

as (3)

, a) dt

where

W ( , a) is a scaled replica of the fundamental mother wavelet; the dilation determines the width of the wavelet and this controls the resolution. The S–transform is obtained by multiplying the CWT with a phase factor as: (4) S ( , f ) exp(i 2 f ) W ( , a) where the mother wavelet for this particular case is defined as (t , f )

f 2

exp (

t2 f 2 ) exp ( i 2 ft ) 2

(5)

In the equation just shown, the dilation factor is the inverse of the frequency. Thus, the final form of the continuous S– transform is obtained as S( , f)

and

h (t )

the

(f) T

width 1 f

f

exp (

2

of

the

(

t )2 f 2 ) exp ( i 2 ft )dt 2

Gaussian

(6) window is : (7)

IV. SIMULATED RESULTS AND DISCUSSIONS This section presents the performance of above discussed techniques for power quality disturbance detection in gridconnected wind power system under various operating scenarios. The various operating scenarios of disturbances are created for study in MATLAB/SIMULINK. The parameters of the components used for simulation are given in the appendix. The voltage signal is captured from the PCC. The voltage signal is then passed through Haar as mother wavelet and S-transform to detect the disturbances. In the simulation part, the extracted voltage signal (original signal) is taken for 2000 samples while the corresponding approximate and detail wavelet coefficients are taken for 1000 samples ,i.e., half the samples of that of the extracted signal. Hence as shown in the graphical results, the detection instants are observed at half of the samples of

3 extracted voltage signal. Fig. 2 shows the extracted voltage signal with notch and its S-transform contour is shown in Fig.3. The corresponding approximate and detail coefficients at every sample obtained by wavelet transform using Haar as mother wavelet is shown in Fig.4. Then the detection of voltage notch under 20 dB noise conditions is shown in Fig.5, 6 & 7 respectively which clearly reflects the advantages of S-transform while Haar wavelet fails to localize the disturbance. Similar observations were seen in Fig. 8, 9 & 10 and Fig.11, 12 & 13 for voltage swell

scenario under normal and 20 dB noise conditions respectively. It can be seen that S-transform contours clearly detecting and localizing the disturbance instants signal under both without and with noise conditions while wavelet transform fails under noise conditions. Exactly similar observations can be analyzed with other disturbances like voltage sag, momentary interruptions and oscillatory transients whose results are not presented due to page limitations. Approx. coef. for haar 2

1

amplitude

0 0.5

-2 0

0

100

200

300

400

500

600

700

800

900

1000

700

800

900

1000

Detail coef. for haar 0.5

-0.5 -1

0

500

1000 sample

1500

2000

0

Fig. 2 Voltage signal with notch.

-0.5

0

100

200

300

400

absolute value of ST matrix

400

500 sample

600

Fig. 7 Detection by Haar wavelet transforms with noise.

300 200

2 100

400

600

800

1000 sample

1200

1400

1600

1800

2000

Fig. 3 S-transform contour.

amplitude

1 200

0 -1

Approx. coef. for haar 2

-2

0

200

400

600

800

0

1200

1400

1600

1800

2000

Fig. 8 Voltage signal with swell. 0

100

200

300

400 500 600 Detail coef. for haar

700

800

900

1000

0.5 0 -0.5

0

100

200

300

400

500 sample

600

700

800

900

1000

Fig. 4 Detection by Haar mother wavelet transforms.

absolute value of ST matrix

-2

1000 sample

20 18 16 14 12 200

400

600

800

1

1400

1600

1800

2000

Fig. 9 S-transform contour.

0.5

amplitude

1000 1200 sample

Approx. coef. for haar 2

0

0 -0.5

-2 -1

0

200

400

600

800

1000 sample

1200

1400

1600

1800

100

200

300

400 500 600 Detail coef. for haar

700

800

900

1000

0

100

200

300

400

700

800

900

1000

1600

1800

2000

0.05

Fig. 5 Voltage signal with notch and 20 dB noise.

0

350

-0.05

300 250

500 sample

600

Fig. 10 Detection by haar mother wavelet transforms.

200

2

150

amplitude

absolute value of ST matrix

0

2000

100 50 200

400

600

800

1000 sample

1200

Fig. 6 S-transform contour with 20 dB noise.

1400

1600

1800

0

2000

-2

0

200

400

600

800

1000 sample

1200

1400

Fig. 11 Voltage signal with swell & 20 dB noise.

absolute value of ST matrix

4 VI. APPENDIX

20 18 16

TABLE I :

14

RATING OF THE GRID-CONNECTED WIND SYSTEM

12 200

400

600

800

1000 1200 sample

1400

1600

1800

2000

Fig. 12 S-transform contour with 20 dB noise.

Wind energy conversion system

Active power :1 MW, rated speed :12 m/s, rated voltage 575V, frequency :50Hz

Approx. coef. for haar 2 0 -2

VII. REFERENCES 0

200

400

600

800

1000

800

1000

Detail coef. for haar 0.1 0 -0.1

0

200

400

600 sample

Fig. 13 Detection by haar wavelet transforms with noise.

V. CONCLUSION This paper has considered the study on detection of power quality disturbances in grid-connected wind energy conversion system using wavelet and S-transform techniques under various scenarios. The variation in voltage signal is observed through wavelet and S-transform under different scenarios. The contours of S-transform suggested not only the detection of power quality events, but also its classification on the type of disturbances. The simulated results clearly show the advantages of S-transform as comparison to wavelet transform in detecting and localizing the disturbances even under 20 dB noise conditions.

[1] O.C. Onara, M. Uzunoglua, M.S. Alama, “Modeling, control and simulation of an autonomous wind turbine/photovoltaic/fuel cell/ultracapacitor hybrid power system”, Journal of Power Sources , vol.185, no. 2, pp. 1273-1283, 2008. [2] Seul-Ki Kim, Jin-Hong Jeon, Chang-Hee Cho, Jong-Bo Ahn, and SaeHyuk Kwon, “Dynamic Modeling and Control of a Grid-Connected Hybrid Generation System With Versatile Power Transfer”, IEEE trans. on ind. Electr. Vol.55, no. 4, 2008. [3] J.A. Pecas Lopes, N. Hatziargyriou, J. Mutale, P. Djapic, N. Jenkins, “Integrating distributed generation into electric power systems: A review of drivers, challenges and opportunities”, Electric Power Systems Research 1189–120, 2007. [4] Huang SJ, Hsieh CT. “Coiflet wavelet transform applied to inspect power system disturbances-generated signals”. IEEE Trans Aerospace Electron Syst , vol. 38,no.1, pp. 204–210, 2002. [5] Cheng-Tao Hsieh, Jeu-Min Lin & Shyh-Jier Huang, “Enhancement of islanding-detection of distributed generation systems via wavelet transform-based approaches”, Electr. Power and Energy Syst., ELSEVIER, vol.30, pp. 575–580, 2008. [6] R. G. Stockwell, L. Mansinha, and R. P. Lowe, “Localization of the complex spectrum: The S– transform,” IEEE Trans. Signal Processing ,vol. 44 , pp. 998–1001, 1996. [7] C.N. Bhende, S. Mishra and B.K Panigrahi, “Detection and classification of power quality disturbances using S-transform and modular neural network”, EPSR, ELSEVIER, pp.122-128, 2007. [8] T. Ackermann, Wind power in power systems, Chichester: Wiley, 2005. [9] A. Tapia, G. Tapia, J.X. Ostolaza, J.R. Saenz, “Modeling control of a wind turbine driven doubly fed induction generator”, IEEE Trans. Energy Convers., vol.18, no.2, pp. 194–204, 2003.