ASTM A-123. CONSTRUCTION: Arc welded. TRAY SERIES: Series 2 (5" tangent
). ENGINEERING INFORMATION. TRAY DESIGN: Construction and markings.
PW Cable Tray TRAY SYSTEM NUMBER RAIL CROSS SECTION
1E53RS Steel, Hot-dip galvanized
FLANGE 13/4"
G
41/8" RUNG
SIDE RAIL 5"
RUNG CROSS SECTION 1.00"
[
[
0.28"
Legrand/Cablofil trays marked with CSA load class have been tested (loading, finish and electrical) by UL to CSA standard
0.97"
0.28"
CONNECTOR
Classified by UL as equipment grounding conductors per NEC 392.7. (UL File No. E60796)
126 22.2 .
GENERAL INFORMATION
ENGINEERING INFORMATION
NEMA TRAY TYPE:
Two Rail Ladder
NEMA CLASS:
20C
CSA CLASS:
D, 6M
TRAY DESIGN: Construction and markings are per the latest edition of NEMA Standards Pub. VE1, CSA C22.2 No. 126.
MATERIAL:
Commercial quality steel / ASTM A-1008 / A-1011
SIDE RAIL:
5" high with 1 3/4" top flange
LOAD DEPTH:
4"
BOTTOM:
1" wide box rung
FINISH:
Hot-dip galvanized after fabrication / ASTM A-123
CONSTRUCTION:
Arc welded
TRAY SERIES:
Series 2 (5" tangent)
TRAY WIDTH (IN.)
TRAY WEIGHT* (LBS./FT.)
6
4.92
9
5.11
12
5.29
18
5.65
24
6.02
30
6.38
36
6.75
TRAY GROUNDING CAPABILITY: Classified as an equipment grounding conductor per N.E.C. 392.7 with a maximum 400 ampere rating. UL Cross Sectional area: 1.00 in2 CONNECTORS: Supplied in pairs with hardware. Splice resistance is less than 0.00033 ohms. Standard hardware: 3/8 in. cadmium-plated with yellow zinc topcoat. Stainless steel hardware is available upon request. MECHANICAL PROPERTIES: One rail: I x-x = 3.1670in3 S x-x = 1.4398in4
*Based on 9" rung spacing
SAFE LOAD DATA (LBS./FT.) / SUPPORT SPAN (FT.) / DEFLECTION (IN.)
PW Cable Tray TRAY SYSTEM NUMBER RAIL CROSS SECTION
1E53SC Steel, Hot-dip galvanized
FLANGE 13/4"
G
43/8" BOTTOM
SIDE RAIL 5"
BOTTOM CROSS SECTION Classified by UL as equipment grounding conductors per NEC 392.7. (UL File No. E60796)
0.88" 0.50" 2.19"
CONNECTOR
GENERAL INFORMATION
ENGINEERING INFORMATION
NEMA TRAY TYPE:
Solid Corrugated
NEMA CLASS:
20C
CSA CLASS:
N/A
TRAY DESIGN: Construction and markings are per the latest edition of NEMA Standards Pub. VE1.
MATERIAL:
Commercial quality steel / ASTM A-1008 / A-1011
SIDE RAIL:
5" high with 1 3/4" top flange
LOAD DEPTH:
4"
BOTTOM:
Solid Corrugated
FINISH:
Hot-dip galvanized after fabrication / ASTM A-123
CONSTRUCTION:
Resistance welded
TRAY SERIES:
Series 2 (5" tangent)
TRAY WIDTH (IN.)
TRAY WEIGHT (LBS./FT.)
6
5.40
9
5.86
12
6.31
18
7.23
24
8.14
30
9.05
36
9.96
TRAY GROUNDING CAPABILITY: Classified as an equipment grounding conductor per N.E.C. 392.7 with a maximum 400 ampere rating. UL Cross Sectional area: 1.00 in2 CONNECTORS: Supplied in pairs with hardware. Splice resistance is less than 0.00033 ohms. Standard hardware: 3/8 in. cadmium-plated with yellow zinc topcoat. Stainless steel hardware is available upon request. MECHANICAL PROPERTIES: One rail: I x-x = 3.1670in3 S x-x = 1.4398in4
SAFE LOAD DATA (LBS./FT.) / SUPPORT SPAN (FT.) / DEFLECTION (IN.)
PW Cable Tray TRAY SYSTEM NUMBER RAIL CROSS SECTION
1E53SF Steel, Hot-dip galvanized
FLANGE 13/4"
G
SOLID 47/8" FLAT
SIDE RAIL 5"
CONNECTOR Classified by UL as equipment grounding conductors per NEC 392.7. (UL File No. E60796)
GENERAL INFORMATION
ENGINEERING INFORMATION
NEMA TRAY TYPE:
Solid Flat
NEMA CLASS:
20C
CSA CLASS:
N/A
TRAY DESIGN: Construction and markings are per the latest edition of NEMA Standards Pub. VE1.
MATERIAL:
Commercial quality steel / ASTM A-1008 / A-1011
SIDE RAIL:
5" high with 1 3/4" top flange
LOAD DEPTH:
4"
BOTTOM:
Solid Flat
FINISH:
Hot-dip galvanized after fabrication / ASTM A-123
CONSTRUCTION:
Resistance welded
TRAY SERIES:
Series 2 (5" tangent)
TRAY WIDTH (IN.)
TRAY WEIGHT (LBS./FT.)
6
5.72
9
6.27
12
6.82
18
7.92
24
9.02
30
11.37
36
12.72
TRAY GROUNDING CAPABILITY: Classified as an equipment grounding conductor per N.E.C. 392.7 with a maximum 400 ampere rating. UL Cross Sectional area: 1.00 in2 CONNECTORS: Supplied in pairs with hardware. Splice resistance is less than 0.00033 ohms. Standard hardware: 3/8 in. cadmium-plated with yellow zinc topcoat. Stainless steel hardware is available upon request. MECHANICAL PROPERTIES: One rail: I x-x = 3.1670in3 S x-x = 1.4398in4
SAFE LOAD DATA (LBS./FT.) / SUPPORT SPAN (FT.) / DEFLECTION (IN.)
PW Cable Tray TRAY SYSTEM NUMBER RAIL CROSS SECTION
1E53VC Steel, Hot-dip galvanized
FLANGE 13/4"
G
43/8" BOTTOM
SIDE RAIL 5"
BOTTOM CROSS SECTION Classified by UL as equipment grounding conductors per NEC 392.7. (UL File No. E60796)
0.88" 0.50" 2.19"
CONNECTOR
GENERAL INFORMATION
ENGINEERING INFORMATION
NEMA TRAY TYPE:
Vented Corrugated
NEMA CLASS:
20C
CSA CLASS:
N/A
TRAY DESIGN: Construction and markings are per the latest edition of NEMA Standards Pub. VE1.
MATERIAL:
Commercial quality steel / ASTM A-1008 / A-1011
SIDE RAIL:
5" high with 1 3/4" top flange
LOAD DEPTH:
4"
BOTTOM:
Vented Corrugated
FINISH:
Hot-dip galvanized after fabrication / ASTM A-123
CONSTRUCTION:
Resistance welded
TRAY SERIES:
Series 2 (5" tangent)
TRAY WIDTH (IN.)
TRAY WEIGHT (LBS./FT.)
6
5.40
9
5.86
12
6.31
18
7.23
24
8.14
30
9.05
36
9.96
TRAY GROUNDING CAPABILITY: Classified as an equipment grounding conductor per N.E.C. 392.7 with a maximum 400 ampere rating. UL Cross Sectional area: 1.00 in2 CONNECTORS: Supplied in pairs with hardware. Splice resistance is less than 0.00033 ohms. Standard hardware: 3/8 in. cadmium-plated with yellow zinc topcoat. Stainless steel hardware is available upon request. MECHANICAL PROPERTIES: One rail: I x-x = 3.1670in3 S x-x = 1.4398in4