Single-phase Cap Start-Cap Run Motors - Rotor UK

37 downloads 3108 Views 41KB Size Report
Capacitor Start-Capacitor Run Motors. Connection Diagram. 4APCC. L1. N. E. L1 . N. E. To change direction of rotation simply re-position the 2 metal links in theĀ ...
Single-Phase 4APCC Capacitor Start-Capacitor Run Motors Connection Diagram

02

01

Z2

02

START WINDING

U2

Z1

U1

Z1

U1

MAIN WINDING

Z2 START WINDING

01

U2

MAIN WINDING

L1

N

E

L1

N

E

To change direction of rotation simply re-position the 2 metal links in the terminal box. In order to use a change-over switch it is necessary to reconnect the internal termination on the terminal block in the following way: The re-connection must be carried out by a qualified electrician ! ROTOR (UK) LIMITED cannot be held responsible for any damages caused by incorrect wiring. 01

02

MAIN WINDING

START WINDING

Z1

U1

L

1. Disconnect Start Winding cable from Z2 and connect it to 02

Z2

2. Disconnect Main Winding cable from U1 and connect it to Z2

U2

N

L(N)

Supply L to U1 at all times. Supply N to Z1 at all times. Swap L and N to U2 and Z2 to change direction of rotation.

N(L)

IMPORTANT ! Always check the motor nameplate for correct voltage and the inside of the terminal box lid for the correct wiring diagram. Ask if in doubt ! Incorrect wiring will damage the motor and invalidate the Warranty! ROTOR (UK) LIMITED, 16 Everitt Close, Denington Industrial Estate, Wellingborough NN8 2QF Tel 01933 230900 Fax 01933 272152 [email protected] www.rotor.co.uk

Z1

C

C

Z1

START WINDING

Z2

U1

U2

C

C

U2

Z2

U1

MAIN WINDING

L1

START WINDING

Single-Phase 7AACC Capacitor Start-Capacitor Run Motors Connection Diagram

MAIN WINDING

N

E

L1

N

E

To change direction of rotation simply re-position the 2 metal links in the terminal box. In order to use a change-over switch it is necessary to reconnect the internal termination on the terminal block in the following way: The re-connection must be carried out by a qualified electrician ! ROTOR (UK) LIMITED cannot be held responsible for any damages caused by incorrect wiring. Z1 MAIN WINDING

N(L)

Z2

U2

L

1. Disconnect Start Winding cable from Z1 and connect it to C (the middle C) 2 Disconnect Main Winding cable from U2 and connect it to Z1

START WINDING

U1

L(N)

C

C

Supply L to Z2 at all times. Supply N to U2 at all times. Swap L and N to Z1 and U1 to change direction of rotation.

N

IMPORTANT ! Always check the motor nameplate for correct voltage and the inside of the terminal box lid for the correct wiring diagram. Ask if in doubt ! Incorrect wiring will damage the motor and invalidate the Warranty! ROTOR (UK) LIMITED, 16 Everitt Close, Denington Industrial Estate, Wellingborough NN8 2QF Tel 01933 230900 Fax 01933 272152 [email protected] www.rotor.co.uk