NEMA Freedom Starters Wiring Diagrams

February 1999

1-77

Non-reversing Starter Non-reversing Starter — Single-Phase Non-combination Remote Pilot Devices

Connections for Non-reversing Starter

2-Wire Control

Figure 1 Front View of Panel 1 L1

3/14 1 Not for Use with Auto Reset OL Relays

”C“

3 L2

1 A1

3-Wire Control Start

A2

T2

M 3/14 1-Phase Motor 98

When More Than One Pushbutton Station Is Used, Omit Connector ”A“ and Connect per Sketch Below

97 OL

3/14 2/13 1

Stop

2/T1 T1 2

”A“

Separate Control Remove Wire “C” if Supplied and Connect Separate Control Lines to the Number 1 Terminal on the Remote Pilot Device and to the Number 96 Terminal on the Overload Relay

96 Reset

Start

Stop

T1

2/13

3/14 2/13 1

Stop

Start

AC Lines

6/T3

4/T2

95

T2 4

260803 D1

Non-reversing Starter — Combination

3 4

2

Red

Figure C 3-Position Selector Switch Yellow 3/14 To Coil Hand Terminal ”A1“ Black 3 Auto 3 Remote 4 4 Switch 1 Red

Figure F START/STOP with Pilot Light Connect to ”A1“ and ”A2“ Terminals X1 Black / White X2 Black / White 2/13 Start (ON) 3/14 3 4 Stop (OFF)

2

1

2-Wire Control 3/14 1 Not for Use with Auto Reset OL Relays.

PG.3.02.T.E

Primary Connections

L3 H1 X1 CPT

4 H4 D.S. or C.B. Disconnecting Means

Omit This Connector 3 if Figure 2 1 Is Used L1 L2 1

5 L3

A1 A2

Local Control (Flange Mounting if Used)

“C”

H2 H3

2/13

XF

1

1

Secondary Connections

X2

See Figures A, B, C, D, E and F

M

G

1 3 5 L1 L2 L3

M

A1 A2

96 OL Reset 95

Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

3/14 98

OL

Remote Control When More Than One 3-Wire Pushbutton Station Is Used, Control Omit Connector “A” and Connect per Sketch Below Start 3/14 Start Start 2/13 Stop 3/14 1 2/13 Stop 1 “A”

Remove Wire “C” (Figure 1) if Used and Connect as Shown Below. (All Other Starter Wires Remain as Shown in Figure 1)

Fuse Fuse

L1 L2

1

Combined Remote and Local for Figures 1 and 2 Local Remote Start (ON) 3/14 2/13 Start 4 3 Stop (OFF) Stop 1 2 1 Omit Connector

Figure 2 Fusible Control Transformer

CPT Fusible Control Transformer (If Used) See Figure 2

X1 Black / White X2 Black / White

Black 3/14 1 Start (ON) 1

Connections for Starters Figure 1 Front View Diagram

Fuse

Connections for Control Stations Local Control Figure A Figure D START/STOP Pushbuttons 2-Position Selector Switch Yellow 2/13 Yellow 3/14 Start (ON) Hand Black Black 3/14 1 3 4 3 Auto Stop (OFF) Red 2 4 Red Red 1 1 1 2 Figure E Pilot Light (Motor RUN) Figure B Connect to Coil Terminals START/STOP Selector Switch ”A1“ and ”A2“

2/ 4/ T1 T2

6/ T3

T1 T2 4 2

T3 6

T1 T2

T3

97 96 Reset 95

Motor Separate Control Remove Wire “C” if Supplied and Connect Separate Control Lines to the Number 1 Terminal on the Remote Pilot Device and to the Number 96 Terminal on the Overload Relay

Field Conversion to 1-Phase Add Dotted 1 3 5 Connection L2 L3 L1 A1 A2

M

OL 2/ 4/ T1 T2 T1

6/ T3 T2

T1

T2

Motor 260878 D4

NEMA Freedom Starters Wiring Diagrams

1-78

February 1999

Reversing Starter Reversing Starter — Non-combination Figure 1 Front View Diagram AC Lines Wire “F” Used with Local Control 3 1 5 Pushbuttons L2 L1 L3

Remote Control Stations

Hold Down Pushbutton

S.P.D.T. Switch Forward

Forward

3 1

3 1

Reverse

5

Starter Elementary Diagram

Contactors “F” and “R” are Mechanically Interlocked

Lines L1 L2 L3

F

4 1

R

2

F

5

Reverse Pushbutton

7 3

F

F

AC Motor

OL

R 98

Pushbutton with FORWARD and REVERSE Buttons Electrically Interlocked

T2 4

T1 2

Forward 7 RLS 5

2 3 T1

T2

T3

AC Motor

97 “C” 96 Reset 95

OL 6/ T3

4/ T2

2/ T1

4 5 1

T3

R 6

5

5

Rev.

T1 T2

OL

“B”

1

Stop

4

R

5 Stop

A2

3

3 2 4

Rev.

A1

A2

A1

2

Forward

OL

“A”

Forward

Stop Reverse 1

“C”

6

F

T3 6

When Limit Switches Are Used, Omit Connectors 3 “A” and “B” and Connect per Dotted Lines

(If Used)

5

R

FLS

OL 95 96

A2 R A1

F

RLS 4

A1 F A2

R

FLS

3

2

7

6

Separate Control Remove Wire “C” if Supplied and Connect Separate Control Lines to the Number 1 Terminal on the Remote Pilot Device and to the Number 96 Terminal on the Overload Relay

260844 D2

Reversing Starter — Combination Pushbutton

Forward 3

3 2 4

Rev.

1 5 Reverse

2 3 Stop

1 4 5

3 4

Blue

Reverse 3 4

Hold Down Pushbutton

Stop

Forward

1 2

1 Reverse

5

Contactors “F” and “R” are Mechanically Interlocked.

4

Red

95

1 L1

Figure D Pilot Light (REVERSE) Connect to Reverse Coil Terminals “A1” and “A2” X1 Black/ X2 White Black/ White

A1

R

AC Motor

T3

R R

FLS

3

2

(If Used) F

RLS R

A1 F A2

6

F

5

4

H4

OL

H2

95 96

H3 1

H1

X1 XF

A2

A2

A1

2

Local Control (Flange Mounting if Used)

1 4

A1

7 3

F

6

5

R

See Figures A, B, C and D

“B”

3 5

98

2/ T1

Primary Connections

CPT

T1 2

1 Secondary Connections 1 L1

A2 R A1

R

3 5 L2 L3 A1 A2

7 RLS

Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

96 OL Reset 95

97 96

OL

X2

G OFF

Reverse

Wire “F” – Use with Local Control Pushbuttons

3

7

Forward

2

Remove Wire “C” (Figure 1) if Used and Connect as Shown Below (All Other Starter Wires Remain as Shown in Figure 1)

Fuse

“C”

Forward

5 L3

4 1

A2

1

OL

F

3 L2

Figure 2 Fusible Control Transformer

T1 T2

OL

F

D.S. or C.B. Disconnecting Means

5

R

1

4

A1

OL

F

4

Black/ White

Blue 5 3 Reverse

3

Stop Reverse

Red

Figure B 3-Position Selector Switch

Figure 1 Elementary Diagram

1

X1 Black/ X2 White

Black 3 Forward

Lines L1 L2 L3 D.S. or C.B.

5

Red 1

3 1

L1 L2 L3

CPT Fusible Control Transformer (If Used) See Figure 2

Connect to “A1” of Forward Coil and “95” of Overload Relay

Red

Fuse Fuse

Stop

Black 3 Forward Yellow 2

5

Rev.

Figure C Pilot Light (FORWARD)

Figure A Pushbuttons

S.P.D.T. Switch

Forward

Forward

Figure 1 Front View Diagram

Local Control

Remote Control Stations

Pushbutton with FORWARD and REVERSE Buttons Electrically Interlocked

T1

T2

4/ T2 T2 4

6/ T3

“A” “C”

Reset 95

T3 6

When Limit Switches Are Used, Omit Connectors 5 “A” and “B” and Connect per Dotted Lines T3

AC Motor

FLS

3

6

Separate Control Remove Wire “C” When It Is Supplied. Connect Separate Control Lines to the Number 1 Terminal on Remote Pilot Device, and to the Number 95 Terminal on the Overload Relay 260882 D4

PG.3.02.T.E

NEMA Freedom Starters Wiring Diagrams

February 1999

1-79

Cover Control

Non-reversing Cover Control NEMA 1 C400GK Control Options

C400T Control Options Local Control Options (If Used) Refer to Diagram Inside Enclosure for Connections

Local Control Options (If Used) Refer to Diagram Inside Enclosure for Connections Figure A START/STOP Pushbutton

Figure D Pilot Light (Motor RUN)

S.P.S.T. Switch Start

Black “A1” Black 3/14

Black 3/14

Black “A2”

Yellow 2/13 Red 1

Figure E START/STOP with Pilot Light

98

Black “A1”

Stop

Yellow 2/13

Yellow - to Coil A1 Terminal Red 1

Red 1

1

Red 2

Black/ White

Connect to OL Terminal No. 96

NC Interlock (If Used)

Black 3 Auto

3

L1, X1 or 1 1

Stop

NC Interlock Black / X1 White

To Coil

Red 1 4

Wire “C”

Figure G Pilot Light (Motor STOP)

Remote Switch

Yellow - to Coil A1 Terminal

X1

Black/ White

Figure C 3-Position Selector Switch Yellow To Coil Hand

Stop

OL 96 Reset 95

X2

1

Connect to OL Terminal No. 96

4 Red

X2 Black / White

1

260808 D1

260811 D1

Reversing Cover Control NEMA 1 C400GR Control Options

C400T Control Options

Local Control Options (If Used) Refer to Diagram Inside Enclosure for Connections

Local Control Options (If Used) Refer to Diagram Inside Enclosure for Connections

Figure A Pushbutton FORWARD/STOP/REVERSE

Figure B Pilot Light (FORWARD)

Add Connector “F” Between Aux. Contact Terminals 2 and 4

Connect to Terminal A1 of the Left Hand Coil and to Terminal Number 95 of the Overload Relay

Blue

Figure A Pushbuttons

Black

3

Reverse . Red

1

Stop

3 Yellow

2

Forward

1

3

Yellow Blue

Black/White 3 2 5

2

Red

1

Black 3 Forward

Black Blue 5 3 Reverse 4

Figure D Pilot Light (REVERSE) Black/White Connect to Reverse Coil Terminals “A1” & “A2”

X1 X2

Black/White

4 Red

PG.3.02.T.E

X2

Black/White

Red

Black

260810 D1

X1

Red

Figure B 3-Position Selector Switch

3

Connect to “A1” of Forward Coil and “95” of Overload Relay

4

Stop

Figure C Pilot Light (REVERSE) Connect to Terminals A1 & A2 of the Right Hand Contactor

Black

4

Reverse .

Black Black

Figure C Pilot Light (FORWARD)

Connect Wire “F” per Diagram

Forward

5

1

97

Connect to Coil Terminals “A1” & “A2”

Black 3 Start

1

3

L1, X1 or 1

1

OFF Hand or Test

98

Figure G Pilot Light (Motor STOP)

Black 3/14

4

Black/White

Figure E Pilot Light (Motor RUN)

Wire “C”

1 Auto

2

Red 1

Figure B START/STOP Selector Switch

4

Remove Lead from Coil to Terminal Number 3 Remote S.P.S.T. Switch Switch

3

2

Red 1 Figure C 3-Position Selector Switch

1

X2

Black Auto

4

Stop

1

96 Reset 95

Black “A2” Black 3/14

X1

OL

Black 3/14 Start

Figure F Overload Tripped Black/ White

Figure D 2-Position Selector Switch Yellow Hand

Red

97

Figure B 2-Position Selector Switch S.P.S.T. Switch

Hand

3

Black

Black

Stop

Auto

Figure A START/STOP Pushbuttons Yellow 2/13 Start

Figure F Overload Tripped

1

260812 D1

NEMA Freedom Starters Wiring Diagrams

1-80

February 1999

Multispeed Multispeed — 2-Speed 1-Winding Constant Horsepower Figure 1 Motor Connections

Remote Control Stations Figure B Fast

Figure C Fast

4

Constant Horsepower Motor

2

3

6

T4 3

2 T3

Slow

Slow 5

Stop

1

Contact

5

B

A B

1OL 2OL

2S

1OL

F

2OL 1S

T4

1OL 1S

F

2OL

Position Fast OFF Slow X X

F 2 Figure B

Connect Lines Remove Wire “C” When It Is Speed Supplied. Connect Separate L1 L2 L3 Together Control Lines to the Number 1 To Motor Terminals Terminal on the Remote Control Slow T1 T2 T3 T4, T5, T6 Station and the Number 96 Fast T6 T4 T5 Terminal on Overload Relay 2OL.

Front View of Panel AC Lines Wire “F” – Omit This 3 1 5 Used with Local Connection If L2 L3 Control Pushbuttons 1 L1 Figure 2 Is Used

Contactors “F” and “1S” Are Mechanically Interlocked.

1

2S

4

A2

2S 4 5 2 3

4

1 2 A1

5

3

A2

L1

F

Figure C Stop 2

A2

Figure 2

1S

F

1

“C” 98

97 96

1OL

T2

T1

Reset 95

6/ T3

97 96 Reset 95

2OL 2/ T1

4/ T2

6/ T3

4

6

5

TB

T6 T4 T5

6

T3

2S A1 F A2 1OL

3 1S

Fast

Fast 1S A12S A2

1

A1

98

4/ T2

T6

2S

2OL

Fast 95 96 95 96 A1 2S A2 6 1S A1 1S A2 Slow L2 2S A1 F A2 1OL 2OL

F

Slow

2/ T1

T2

1S 3 Fast OFF Slow 5

4

A1

T5

T2

X = Contact Closed

CPT Fusible Control Transformer (If Used) See Figure 2

Constant T1 Horsepower Motor

T3

2S T6

T5 2 Separate Control

3

A 1

1

OFF Slow 3

Starter Elementary Diagram

F

T1

5

4

6 Fast

Lines L1 L2 L3 2S

F

95 96 95 96 6

A11S A2

5

Slow

Control Circuit Transformer (If Used) Remove Wire “C” if Supplied and Connect as Shown Below. CPT H3 H2 4 (All Other Wiring Remains as Shown in Figure 1.) Fuse Primary H4 Connections Fuse H1 5 1 3 L1 L2 L3 Fuse

X2 XF X1 Secondary Connections 1 G 2OL Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

A1 F 96 Reset 95

A2

260819 D3

Multispeed — 2-Speed 1-Winding Constant or Variable Torque Figure 1 Motor Connections

Remote Control Stations Figure B Fast

Figure C Fast

4

2

3

6

3 Slow 5

A 1

B

T4 T1

T5

1

T5

T6

T2

T1

T3

5 Stop

1

T4 T3

4

6 OFF Slow 3

Variable Torque

2

Slow

Fast

Constant Torque

AC Lines L1 L2 L3 S

T6

T2

Starter Elementary Diagram Variable Constant 1OL Torque Torque

2F

2OL

S

1OL

1F

2F

2OL

1F T3

S

1OL

2F

2OL

2F

3

T2

T5

T1 Motor T6 T5

T3

T1 T2

T6

2 Separate Control

3

Contact

5

A B

Position Fast OFF Slow X X

X = Contact Closed

Connect Lines Remove Wire “C” When It Is Speed Supplied. Connect Separate L1 L2 L3 Together Control Lines to the Number 1 To Motor Terminals Terminal on the Remote Control Slow T1 T2 T3 Station and the Number 96 Fast T6 T4 T5 T1, T2, T3 Terminal on Overload Relay 2OL.

2

S

4

Contactors “1F” and “S” Are Mechanically Interlocked.

Fast 1F

Slow Figure C

Stop

2

1 4 A1

1F A12FA2 95 96 95 96 Fast

3

5

4 A2

A1 1F

S

2 3 4 5

1

98 2OL 2/ T1 T6

4/ T2 T4

6/ T3 T5

“C” 97 96 Reset 95

98 97 96 Reset 95

1OL 2/ T1

4/ T2

6/ T3 6

S

1F 5

2F

6 A1 S A2

Slow

A2 Figure 2

2F

L2 A21FA1 1OL 2OL

Fast

2

Slow

A2

6

2F A1 S A2

S

2F 3

1

A1

2OL

1F A12FA2 95 96 95 96

Fast OFF Slow 5

Figure B 1

1OL

A21F A1

S

L1

Front View of Panel AC Lines Wire “F” – Omit This 1 3 5 Used with Local Connection If L1 L2 L3 Control Pushbuttons 1 Figure 2 Is Used

CPT Fusible Control Transformer (If Used) See Figure 2

T4

T4

1 2

3

T1 T2 T3

TB

Control Circuit Transformer (If Used) Remove Wire “C” if Supplied and Connect as Shown Below. CPT H3 H2 4 (All Other Wiring Remains as Shown in Figure 1.) Fuse Primary H4 Connections Fuse H1 5 1 3 L1 L2 L3 Fuse

X2 XF X1 Secondary Connections 1 G 2OL Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

A1 S 96 Reset 95

A2

260818 D3

PG.3.02.T.E

NEMA Freedom Starters Wiring Diagrams

February 1999

1-81

Multispeed Multispeed — 2-Speed 2-Winding Remote Control Stations Figure B Figure C Fast Fast 4

2

3

6

3 Slow

1 5

5

4

H3

H2

Fuse

1

A 1

B

H1

2

1 L1

Fuse X2

3 1

Primary Connections

H4

Fuse OFF Slow

S

1OL

S

1OL

S

1OL

F

2OL

F

2OL

F

2OL

T1 Slow Speed

XF

X1

A1

T2 T11 Fast Speed T12

T13

A2

“C”

1 Secondary Connections

G

Position Contact Fast OFF Slow A X X B

5 L3

3 L2

F

3 5

T3

CPT

4

Stop

Fast

AC Lines L1 L2 L3

2

Slow

6

Starter Elementary Diagram

Figure 2 Control Circuit Transformer (If Used) Remove Wire “C” if Supplied and Connect as Shown Below. (All Other Wiring Remains as Shown in Figure 1)

F

S

2

96 Reset 95

2OL

Figure B

Fast OFF Slow

1 S

4

2OL

95 96 95 96 Fast

Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

1OL

A1 F A2

3

6

Slow

5

F

A1 S A2

S

A1 F A2

X = Contact Closed L1

F

Figure C Stop

2

3

Fast

1OL

1 Slow 4

S

L2

F

A1 S A2

2OL

95 96 95 96

5

Figure 1 Front View of Panel Contactors “S” and “F” Are Mechanically Interlocked. AC Lines 1 3 5 L1 L2 L3

CPT Fusible Control Transformer (If Used) See Figure 2

1

4 NC

“F” (Used with Local Control)

4

A2

A1

2

A2

A1

NC NO

NO 5

5

2

3

F

S

3 “C”

98

98 97 96 Reset

1OL Separate Control 2/ T1

Remove Wire “C” When It Is Supplied. Connect Separate Control Lines to the Number 1 Terminal on the Remote Control Station and the Number 96 Terminal on Overload Relay 20L.

6/ T3

4/ T2 T1

T2

95

T3

97 96

2OL

6

2/ T1 T11

4/ T2 T12

6/ T3

Reset 95

T13

Motor Connections T1

T11

Slow Speed

T3

PG.3.02.T.E

Fast Speed

Motors

T2

T13

T12

260815 D3

1-82

NEMA Freedom Starters Wiring Diagrams

February 1999

Cover Control

Multispeed Cover Control 2-Speed 2-Winding C400GK Control Options

2-Speed 1-Winding CH C400GK Control Options

Figure A 3-Position Selector Switch (2-Wire Control) Fast OFF

Black Yellow

Slow Red

3 1 5

Figure A 3-Position Selector Switch (2-Wire Control) Fast OFF

Black Yellow

Slow Red

3 1 5

2-Speed 1-Winding CT, VT C400GK Control Options Figure A 3-Position Selector Switch (2-Wire Control) Fast OFF

Black Yellow

Slow Red

3 1 5

Figure B Pilot Light (FAST)

Figure B Pilot Light (FAST)

Figure B Pilot Light (FAST)

Connect to Terminal Numbers A1 and A2 of Right Hand Contactor

Connect to Terminal Numbers A1 and A2 of Contactor F

Connect to Terminal Numbers A1 and A2 of Contactor 2F

Black

Black

Black

Black

Black

Black

Figure C Pilot Light (SLOW) Connect to Terminal Number A1 of Left Hand Contactor and Terminal Number 95 of Overload Relay 1OL Black

Figure C Pilot Light (SLOW) Connect to Terminal Number A1 of Contactor 2S and Terminal Number 95 of Overload Relay 1OL Black

Black

Black

Black 260817 D1

Figure C Pilot Light (SLOW) Connect to Terminal Number A1 of Contactor S and Terminal Number 95 of Overload Relay 1OL

Black 260894 D1

260893 D1

PG.3.02.T.E

NEMA Freedom Starters Wiring Diagrams

February 1999

1-83

Cover Control

Multispeed Cover Control 2-Speed 1-Winding CH C400T Control Options Figure A Pushbuttons

Figure C Pushbuttons

Fast Black 3

4 Red

Yellow

Slow 3

2

3

Red

5

Slow

4

5

Stop

4

Red 1

Stop

2 Red

1

2

1

Figure B 3-Position Selector Switch Yellow 3 Fast

3

2

3

2 Blue

4

Fast

4

3

Pilot Light (FAST) Black/White Connect to Terminal Numbers A1 and A2 of Contactor F

Black 5 Slow

X1 X2

Black/White Pilot Light (SLOW)

4

4 Red

Black/White Connect to Terminal X1 Number A1 of Contactor 2S and Terminal Number 95 of X2 Overload Relay 1OL Black/White

1

260896 D1

2-Speed 1-Winding CT, VT C400T Control Options Figure A Pushbuttons Fast Black 3

4 Red

Yellow

Slow 3

Red

3

Red

5

Red

3

4

3

1

Figure B 3-Position Selector Switch Yellow 3 Fast

Black 5 Slow

Red

4 Red

PG.3.02.T.E

1

Slow

4

5 4

Red

Pilot Light (FAST) Black/White Connect to Terminal Numbers A1 and A2 of Contactor 2F

Stop 1

Figure B 3-Position Selector Switch Yellow 3 Fast

X1 X2

Black/White 3

3

Black/White Connect to Terminal X1 Number A1 of Contactor S and Terminal Number 95 of X2 Overload Relay 1OL Black/White 260895 D1

2

1

Black 5 Slow

Pilot Light (SLOW) 4

3

5

2

2

1

2

Red

Stop

2

3

Stop

4

Fast

4

2 Blue

5

1

Yellow

Slow

Slow

4

2

3

Black 4

2

Figure C Pushbuttons

Fast

2

3

Red

3

Fast

4

Stop 1

Figure A Pushbuttons

2 Blue

4

2-Speed 2-Winding C400T Control Options

Figure C Pushbuttons

Pilot Light (FAST) Black/White Connect to Terminal Numbers A1 and A2 of Right Hand Contactor

X1 X2

Black/White Pilot Light (SLOW)

4

4 Red

1

Black/White Connect to Terminal X1 Number A1 of Left Hand Contactor and Terminal Number X2 95 of Overload Relay 1OL Black/White 260816 D1

NEMA Freedom Starters Wiring Diagrams

1-84

February 1999

Reduced Voltage Part Winding — Non-combination Figure 1 Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

Front View Diagram 1

H3 H2 4 Fuse

H4

Fuse

Remote Control Stations

H1

1M 1OL

Fuse XF X1 1

X2

Starter Elementary Diagram AC Lines Select Overload Heater Packs for 50% of Rated L1 L2 L3 Full Load Motor Current. 2M 2OL

CPT

AC Lines 1 3 5 L1 L2 L3

G

2-Wire Control 2

A1

3

1M

TR

1OL 2/ T1

Start

6 5 4 3

3 2 1

7 8 1 2

2M 2OL

T9

1M 1OL

T3

T3

T8

T1

”A“

4/ T2

97 96 Reset 95

6/ T3

T8

T7

T3

XF

CPT

X2 G

Stop 2 Start 3

T9

3 2 1

1M

Motor Connections If Terminals T4, T5 & T6 Are Brought Out, Connect Them Together at Terminal Box.

T7

T3 T2 T9 T8 Typical 6 Lead Delta Motor

Start Stop

T2

T1

98

97 96 2OL Reset 2/ T1 95

6/ T3

A11M A2 1OL A12M A2

8 TR 6

T.C.

2OL

95 96 95 96

2 TR 7 E

T7 T8 T9

T1 T2 T3 T4

T6

T.C. = Timed Closing T.O. = Timed Opening

T5

Wires T1, T2, T3, T7, T8 & T9 Must Have Capacity for 50% of Rated Motor Full Load Current.

T2 T9 T8 Typical 6 Lead Delta Connections

H1 H4

2M

4/ T2

T7

T2

T6

1

When More Than One Pushbutton Station Is Used, Omit Connector ”A“ and Connect per Sketch Below

Stop

T1

T5

1M 1OL

A2

A1

A2

98

3-Wire Control

Start

T7

2M 2OL

3 1 Not for Use with Auto Reset OL Relays

Stop

T1 T4

Wye Motor

260997 D3

Autotransformer — Combination Connections for Starters

Connections for Control Stations

2

Red

Shop Note: Refer to Figure 2. Connect Green Ground Wire to Panel Using Hole Located Adjacent to Transformer Mounting Foot.

2-Wire Control

3-Wire Control Start

3 1 Not for Use with Auto Reset OL Relays.

Stop

Start

Start

Stop

Stop 2 1

3

“A”

1

3 2 1

When More Than One Pushbutton Station Is Used, Omit Connector “A” and Connect per Sketch at Left.

2S

Hand

PS OFF

T.O. 1S

Stop

Omit Connector

2 1

1

100%

80% 65% 50% 0%

100%

80% 65% 50% 0%

8 TR 6 54 1S 55 A1 R A2

T.C.

2

3 A2

2

1

L3

L1 L2 A1

3 3

4 52 A1

A2

52

R 3C 3E 3D

3

L1 L2

3 54

53 A1

98 97 96 B Reset 95 4 T1 T2 T3

1S 53 55 1E 1D 1C

A2

T.O. = Timed Opening T.C. = Timed Closing

2S 5C 5E 5D

L3 2 3

3 53

Local Control (Flange Mounting if Used) See Figures A, B, C, D, E and F

OL

OTT “C” OTT “E” OTT “D” 8 C C D D X2 5C 100% 100% 5E 100% 5D 80% 80% 80% 3C 65% 65% 3E 65% 3D 50% 50% 50% 1C 0% 0% 1E 0% 1D

80% 65% 50% 0%

100%

53 A1 2S A2

Auto-Transformer Overtemp SWs

2S

TB3

7 81 2

4

51 55

R 3C 1S 2S OL T1 1C 5C R T2 3E T3 1S 2S 1E R 5E 3D Motor 1S 2S TBX2 1D 5D Stopped R 7 1S 8 9 10 G Run G On Delay .5-15 Sec. OTT OTT OTT TB1 Stop TB2 Start TB3 2 TR 7 TB4 OL “C” “E” “D” E TB1 95 96 B C D 8 TR 5 51 R 52 A1 1S A2

Auto TB1 TB1

6543

Stop (OFF)

Elementary Diagram RVNR AUTOXFMR (3 Coil) Circuit L1 L1 Breaker 1 2 L2 L2 or Switch L3 L3 3 and Fuse

D.S. or C.B. Disconnecting Means 1 2 3

TR

1

4 3

L1 L2 L3

54 51 TB X2 1 1 2 3 4

3

2

Contactors "1S" and "R" Are Mechanically Interlocked.

L1 L2 L3

Combined Remote and Local for Figures 1 and 2 Remote Local Start (ON) Start

Figure 1 Front View Diagram

CPT H1 Fusible Control XF Transformer (If Used) H4 See Figure 2 X2

Figure 2 Fusible Control Transformer Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

H2 H3 1

Primary Connections

H1 X1 CPT

H4 4 Fuse

Figure F START/STOP with Pilot Light Connect to Terminals ”3“ Figure C and ”4“ on Terminal Board 3-Position Selector Switch 3 X1 Black / White Yellow 3 Hand X2 Black / White 4 2 Start (ON) Black 3 3 3 Auto 3 4 3 Remote Stop (OFF) 4 4 Switch 1 Red 1 1 2 4

Remote Control

Fuse Fuse

Local Control Figure A Figure D START/STOP Pushbuttons 2-Position Selector Switch Yellow Yellow 2 3 Start (ON) Hand Black Black 3 1 3 Auto 2 3 4 Red Stop (OFF) 2 4 Red 1 Red 1 1 2 Figure E Pilot Light (Motor RUN) Figure B Connect to Terminals ”3“ START/STOP Selector Switch and ”4“ on Terminal Board 3 X1 Black / White Black 3 X2 Black / White 3 1 Start (ON) 4

XF

X2 G

1 Secondary Connections L1

T1 T2 T3

Motor

L2

2S

X2

260959 D4

PG.3.02.T.E

NEMA Freedom Starters Wiring Diagrams

February 1999

1-85

Reduced Voltage Wye Delta — Open Transition Combination Connections for Control Stations Local Control Remote Control Figure A Figure D 2-Wire Control 3-Wire Control START/STOP Pushbuttons 2-Position Selector Switch Yellow Yellow Start 3 2 3 Start (ON) Hand 3 1 2 Black Black Not for Use 3 Stop 1 1 3 Auto 3 3 4 with Auto Reset Red OL Relays. 2 4 Red Stop (OFF) Red 1 When More 1 Start Start Than One Figure E 1 2 Pushbutton Pilot Light (Motor RUN) 3 Station Is Figure B Connect to Terminals ”3“ Used, Omit START/STOP Selector Switch and ”4“ on Terminal Board Stop 2 Connector 3 1 “A” and X1 Black / White Black “A” Connect 3 X2 Black / White 3 1 Start (ON) per Sketch 4 at Left. Figure F 1 4 2 Red START/STOP with Pilot Light Connect to Terminals ”3“ Combined Remote and Local Figure C for Figures 1 and 2 3-Position Selector Switch and ”4“ on Terminal Board 3 Remote Local Yellow X1 Black / White 3 Start (ON) Hand X2 Black / White 4 3 2 2 Start Black Start (ON) 4 3 3 3 Auto 3 3 Stop (OFF) 3 4 Remote Stop Stop (OFF) 4 4 Switch 1 1 Red 1 1 2 1 2 Omit Connector

Start

TB3

1S

G

2M

51

T.O. 1S

TB3

8 TR 6

OFF

54

T.C.

Hand

2

3 L3 4 A2

L1 L2 53 A1

1 2

3

2

T4 T5 54 3 52 A1

3

53

3

55 53

Top

T5

T1

52 53

A1 1M A2

55

A1 2M A2

4 L3

51

A2

52

2M T6 T4 T5

Bottom

T6 T4 T5

TBX2

Figure 2

Run

TR 7 E 1S A1 A2

1S T6 T4 T5

See Figures A, B, C, D, E and F

3

L1 L2 55 A1

4 T6 A2

T2 T3 4 95 Select Overload Heater Coils for 58% of Rated Full Load Motor Current

Motor

2

98 97 96 X2 Reset

OL

4 H4

95 96

Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

H2

H1

Primary Connections

H3

X1 CPT XF

T6

1

1

T1

T5

X2

Wires T1, T2, T3, T4, T5 and T6 Must Have Capacity for 58% of Rated Full Load Motor Current

T4

T3

Secondary Connections

T.O.= Timed Opening T.C. = Timed Closing

1S

Motor Connections

Fusible Control Transformer

OL

TB4

1M

PS

Auto

TB1 TB1

1S

Stopped

ON-Delay 1.5-15 Seconds 2

8 TR 5

1M

3 3

Fuse Fuse

8

R

TB1 TB1

1

Select Overload Heater Coils for 58% of Rated Full Load Motor Current 7

TB2

L1 L2 L3 D.S. or C.B. Disconnecting Means 1 2 3

7 81 2

4

Local Control (Flange Mounting if Used)

T1

2M

Stop

X2 1 1 2 3 4

1S T2 T3

1S

L1 L2 L3

51

54

TR

Fuse

6

1S OL

1M

Contactors "2M" and "1S" Are Mechanically Interlocked.

6543

TB

T6

2M

L1 Circuit Breaker 1 2 L2 or Switch L3 and Fuse 3

5

H4

Figure 1 Front View Diagram

XF

CPT Fusible Control Transformer X2 (If Used) See Figure 2

T4

Wye-Delta Open Transition

L1 L2 L3

H1

1M

Elementary Diagram Shop Note: Refer to Figure 2. Connect Green Ground Wire to Panel Using Hole Located Adjacent to Transformer’s Mounting Foot.

Connections for Starters

T2

L1 L2

260960 D4

X2

1M

G

Wye Delta — Closed Transition Combination

Elementary Diagram L1 Circuit Breaker 1 2 L2 or Switch L3 and Fuse 3

Resistor 1M

7

PS TB3 OFF

Hand

PG.3.02.T.E

4 4

7 81 2

3 51

4 3

Resistor

Resistor

T6

1

2

ON-Delay 1.5-15 Seconds 2 TB3

R

L1 L2 L3 Contactors "2M" D.S. or C.B. and "1S" Are Disconnecting Mechanically Means Interlocked. 1 2 3

4 A2

T5 Local Control (Flange Mounting if Used)

51 52

2S T3B

3

L1 L2 54 A1

1

4 L3 2 A2

1M T1A T2A T3A

OL

3

3

2

T4 T5 56 54 52 A1

54

3

55 3

Top

T2

T3

4 T6 A2

1S T6 T4 T5

Bottom

2

3

L1 L2 56 A1

4 L3 A2

2M T6 T4 T5

See Figures A, B, C, D, E and F

3 51

98 97 96 X2 Reset A 95

T1

T2 T3 Stopped

T4

53 A1

T1B T2B

T1

G

53

T1B T2B T3B

1S OL

8

Start 1S

Auto

T3B

T2A T3A

1M

TB1 TB1

TRP 7 81 2

T5

1S

1S

2S T1B T2B

2M

TB1 TB1

53

TR

T1A T2A T3A

T6

T1A

1S Stop

6543

TB X2 1 1 2 3 4

L1 L2 L3

A 6543

T6 T4 T5

Select Overload Heater Coils for 58% of Rated Full Load Motor Current Motor TBX2

Run 7

Figure 2

TR 1 TRP 4 A OL 51 2S 52 A1 A2 1S ON-Delay 2 Sec. (Fixed) TB4 T.O. 95 96 2M 2 1 3 7 53 E Select Overload Heater TRP T.C. Coils for 58% of Rated A1 A2 Full Load Motor Current 2S A1 A2 54 1S 1M 1M 8 TR 6 55 A1 A2 56 T.O.= Timed Opening 2M T.C. = Timed Closing 1S T.C.

Motor Connections

Fusible Control Transformer

E

4 H4 Connections for Dual Voltage Rated Transformer – See Transformer Nameplate

H2 H3

H1

Primary Connections

X1 CPT

Fuse Fuse

2M

Shop Note: Refer to Figure 2. Connect Green Ground Wire to Panel Using Hole Located Adjacent to Transformer’s Mounting Foot. 6

CPT Fusible Control Transformer X2 55 (If Used) See Figure 2

T4

Wye-Delta Closed Transition

5

H4

Figure 1 Front View Diagram

XF

Fuse

L1 L2 L3

Connections For Starters H1

Resistor

Connections for Control Stations Local Control Remote Control Figure A Figure D 2-Wire Control 3-Wire Control START/STOP Pushbuttons 2-Position Selector Switch Yellow Yellow Start 3 2 3 Start (ON) Hand 3 1 2 Black Black Not for Use 3 Stop 1 1 3 Auto 2 3 4 with Auto Reset Red OL Relays. 2 4 Red Stop (OFF) Red 1 When More 1 Start Start Than One Figure E 1 2 Pushbutton Pilot Light (Motor RUN) 3 Station Is Figure B Connect to Terminals ”3“ Used, Omit START/STOP Selector Switch and ”4“ on Terminal Board Stop 2 Connector 3 1 “A” and X1 Black / White Black “A” Connect 3 X2 Black / White 3 1 Start (ON) per Sketch 4 at Left. Figure F 1 4 2 Red START/STOP with Pilot Light Connect to Terminals ”3“ Combined Remote and Local Figure C for Figures 1 and 2 3-Position Selector Switch and ”4“ on Terminal Board 3 Remote Local Yellow Black / White X1 3 Start (ON) Hand X2 Black / White 4 3 2 2 Start Black Start (ON) 4 3 3 3 Auto 3 3 Stop (OFF) 3 4 Remote Stop Stop (OFF) 4 4 Switch 1 1 Red 1 1 2 1 2 Omit Connector

1

XF

T6

1

T3

Secondary Connections

T5

X2

T1 T4 T2

Wires T1, T2, T3, T4, T5 and T6 Must Have Capacity for 58% of Rated Full Load Motor Current

L1 L2 G

1M

X2

260961 D4